Commissioning Instructions
Central Functions
Configuring Central Function for Supply Air Temperature Setpoint Evaluation
5
A6V12006922
Restricted
17 | 21
1. Change the Infrastructure Priority Object.
NOTICE! When configuring a Central Function app type for the first time, the Infrastructure
Priority Objects must be changed. If they are kept as defaults, they can cause alarms to come in
at a Life Safety priority, regardless of the actual status. Settings should be as shown above.
2. Close the application.
3. Add the Central Function device to the building hierarchy