Data Sheet for Product

7
Siemens
A6V11259958_en--_b
Smart Infrastructure
Unrestricted
2020-01-16
Power data
Power supply
Operating voltage AC 24 V -15%/+20%
Frequency 50/60 Hz
Internal fuse 4 A irreversible
Transformer with secondary current limitation of max. 10 A
or external secondary current fuse
Non-renewable fuse
Circuit breakers
Max. 10 A, (Class 2, 4A)
Max. 13 A, characteristic B, C, D as per EN 60898
Apparent power (VA) for transformer design
Base load
including I/O
without load
by field
devices
Max. output
load Triac at
500 mA each
Max. load for
AC 24 V field
supply at
200 mA
Max. load KNX
PL-Link at
50 mA
Max. load for
DC 24 V field
supply at 100
mA
Power
consumption
including
connected field
devices
DXR2.E10P 11 4 x 12 = 48 - 4 - 63
NOTE:
To calculate the total VA, add the Base Load + the number of Triacs + field supplies+ KNX PL-
Link devices.
This cannot exceed the maximum power consumption. See the
Wiring Guidelines
for more
information.
Inputs
Resistance sensor, analog (inputs X...)
Type
Range (over range)
Resolution
AI 1000 Ohm *) 1 k (0...1.05 k) 1
AI 2500 Ohm *) 2.5 k (0...2.625 k) 2.5
AI 10 kOhm *) 10 k (0...10.5 k) 10
AI 100 kOhm *) 100 k (0...105 k) 100
Temperature measurement, analog (inputs X...)
Type
Range (over range)
Resolution
AI PT1K 375 (NA) *)
-40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
0.025 K
0.045 °F
AI PT1K 385 (EU) *)
-40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
0.025 K
0.045 °F
AI (LG-)Ni1000 *)
-40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
0.025 K
0.045 °F
AI Ni1000 DIN *)
-40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
0.025 K
0.045 °F
AI T1 (PTC) *)
-40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
0.100 K
0.18 °F
AI NTC10K (Type II)
-40...70 °C (-45...75 °C)
-40...158 °F (-49...167 °F)
0.025 K (@ 25 °C)
0.045 °F (@ 77 °F)
AI NTC100K
-10...70 °C (-15...75 °C)
14...158 °F (5...167 °F)
0.025 K (@ 25 °C)
0.045 °F (@ 77 °F)
*) A fixed value of 1 is calibrated to correct line resistance.