Commissioning Instructions
12
Restricted
A6V12093876
Central Room Operation Distribution (CenROpDstr01)
IMPORTANT! DO NOT use this function CenROpDstr01
Central Operating Mode Delay (CenOpModDly11…13)
This application function is used to program a delay in the signals sent by the Cen-
tral Operating Mode functions. All elements of the Central Operating Mode group
(i.e. the outputs of CenOpMod11 and the included AFs) are distributed to the rooms
after a configured delay.
The delayed AFs are used to distribute to the rooms but cannot be used for distribu-
tion to subordinate AFs CenOpModDly11…13. The AFs receive the values from
CenOpMod11. Each change is saved in a buffer. The AFs then read back the values
from the buffer after the delay time (CenOpModDly1…3) expires and decodes and
distributes them to the connected group members.
By having three separate delays, each group and its members can receive com-
mands at different times.
Point Database
Description
BACnet Name
(Abbreviated name)
Type
Default Value
Central Operating Mode Delay 1…3
CenOpModDly1…3
UCnfVal
CenOpModDly1: 10 [s]
CenOpModDly2: 20 [s]
CenOpModDly3: 30 [s]