User Manual

6
Siemens
A6V11259958_en--_b
Smart Infrastructure
Unrestricted
2020-01-16
Operation
The outputs have no electricity when power fails.
USB communications failure can be caused by weak or incorrect grounding at DXR 24 V power
termination. (The power terminal labeled must be connected to earth ground.)
Disposal
The device is considered an electronics device for disposal in terms of European
Directive 2012/19/EU and may not be disposed of as domestic garbage.
Dispose of the device through channels provided for this purpose.
Comply with all local and currently applicable laws and regulations.
Warranty
Technical data on specific applications are valid only together with Siemens products listed
under "Equipment combinations". Siemens rejects any and all warranties in the event that third-
party products are used.
Technical data
Housing
Color RAL 7035 (light-gray)
Dimensions
201 mm (7.91 in) x 136.94 mm (5.39 in) x 81.72 mm (3.22
in)
Weight
DXR2.x10
Packaging
ca. 831 g (29.3 oz)
ca. 200 g (7.05 oz)
Function data
Processor Texas Instruments AM3352, 300 MHz
RAM
128 MByte SDRAM (DDR3)
512 MByte NAND Flash
Communication
A/D Resolution (analog in)
D/A Resolution (analog out)
14 Bits
12 Bits
Actuator
Torque 88 lb-in (10 Nm)
Runtime for 90°opening or closing
Nominal angle of rotation
Maximum angular rotation
90 sec. (50 Hz or 60 Hz)
90°
95°
Shaft size
3/85/8 inch (816 mm) Dia.
1/41/2 inch (613 mm) Dia.
Minimum shaft length 3/4 inch (20 mm)