Conformity
Ambient conditions and protection classification
Classification per IEC/EN 60730
Function of automatic control devices
Pollution degree
Overvoltage category
Type 1
2
III
Design type
Device suited for use with equipment of safety classes I
and II
Degree of protection of housing to IEC EN 60529
Room automation station
IP20
IP30
Climatic ambient conditions
● Transport (packaged for transport) as per IEC
EN 60721-3-2
● Operation as per IEC/EN 60721-3-3
● Class 2K3
Temperature -25...70 °C (-13... 158 °F)
Air humidity 5...95% (non-condensing)
● Class 3K5
Temperature -5...50 °C (23... 122 °F)
Air humidity 5...95% (non-condensing)
Mechanical ambient conditions
Transport as per IEC/EN 60721-3-2
Operation as per IEC/EN 60721-3-3
Class 2M2
Class 3M2
Standards, directives and approvals
Product standard IEC/EN 60730-1
Automatic electronic controls for household and similar
use
Product family standard EN 50491-2, EN 50491-3, EN 50491-5
General requirements for Home and Building Electronic
Systems (HBES) and Building Automation and Control
Systems (BACS)
Electromagnetic compatibility For residential, commercial, and industrial environments
EU conformity (CE)
EU declaration of conformance DXR2.. AC 24 V, see
CM1T9204xx_2
RCM conformity
RCM declaration of conformance DXR2.. see
CM1T9204xx_C1
EAC compliance Eurasien compliance for all DXR2.xxx-xxxB variants
UL Approbation
Federal Communications Commission
UL as per UL864, http://ul.com/database
UL1995 94v flammability
cUL as per CSA – C22.2 No. 205
FCC CFR 47 Part 15 Class B
BACnet BTL-AAC BACnet Protocol Revision 13
Environmental compatibility
The product environmental declaration () contains data on
environmentally compatible product design and
assessments (RoHS compliance, materials composition,
packaging, environmental benefit, disposal).
See Section
Product documentation
.
Quality ISO 9001 (Quality)