Commissioning Instructions

Step 8 Fault detection and diagnostics parameters
14
Step 8 Fault detection and diagnostics
parameters
This step covers the addition and configuration of paramaters for:
Supply flow fault and diagnostics
Supply heat temp fault and diagnostics
Extract flow fault and diagnostics
Dual Duct flow fault and diagnostics
To add additional parameters to the Default values, left click on button in
the upper right of the Configuration Tab screen. Select %RSegm%’AuxFnct
Add the following to “Additional parameters as needed:
NRCA-MCH13A (Revised 6/17) section C (Functional Testing for Zone Terminal Units)
contains 7 steps/tests which in can result in 3 possible BACnet Point alarm/fault.
Please note that steps 1-6 result in a fault being reported via one of the 3 possible
BACnet Point faults. Step 7 tests functionality and will not result in a fault alarm.
Step
Test
BACnet Point Name
BACnet Obj
1
Sensor Drift/failure
SuAirFlFlt
SU FLOW FLT
2
Damper/Actuator fault damper stuck open
SuAirFlFlt
SU FLOW FLT
3
Damper/Actuator fault damper stuck closed
SuAirFlFlt
SU FLOW FLT
4
Valve/Actuator fault (for system with HW reheat)
HTSuFlt
SU H TMP FLT
5
Feedback loop tuning fault (unstable airflow)
SuUnstblCtlFlt
SU UNSTB FLT
6
Disconnected inlet duct
SuAirFlFlt
SU FLOW FLT
7
Discharge air temp sensor
NA Functionality Test