Application

Point Database
96
Siemens Industry, Inc.
A6V11692053
Smart Infrastructure Building Products
2019-04-01
#
Descriptor
Object
Type
Instan
ce #
Desigo Name
Description
Default
Value
Units
Enumeration
On
Text
Off
Text
89
PLNK STATUS
CmnEvt
4
PlnkBusSta
KNX PL-Link bus
state
Normal
--
1:Normal
2:IntervAc
3:Fault
4:Alarm
5:FltAlrm
--
--
90
RM STATUS
CmnEvt
12
RSta
Room state
Normal
--
1:Normal
2:IntervAc
3:Fault
4:Alarm
5:FltAlrm
--
--
91
SEGM STATUS
CmnEvt
13
RSegmSta
Room segment state
Normal
--
1:Normal
2:IntervAc
3:Fault
4:Alarm
5:FltAlrm
--
--
92
RM OP MODE
MPrcVal
17
ROpMod
Room operating mode
Protect
--
1:Protect
2:Economy
3:PrComfrt
4:Comfort
--
--
93
GREEN LEAF
MPrcVal
19
REei
Energy efficiency
indication room
Undef
--
1:Undef
2:Poor
3:Satisf
4:Good
5:Excel
--
--
94
RM LGT
GRNLF
MCalcVal
20
RLgtEei
Room energy
efficiency ind.lighting
Undef
--
1:Undef
2:Poor
3:Satisf
4:Good
5:Excel
--
--
95
RM SHD
GRNLF
MCalcVal
21
RShdEei
Room energy
efficiency ind.shading
Undef
--
1:Undef
2:Poor
3:Satisf
4:Good
5:Excel
--
--
96
RMHVAC
GRNLF
MCalcVal
24
RHvacEei
Room energy
efficiency indication
HVAC
Undef
--
1:Undef
2:Poor
3:Satisf
4:Good
5:Excel
--
--
97
H.C STATE
MCalcVal
25
HCSta
Heating/cooling state
Neither
--
1:Neither
2:Heating
3:Cooling
--
--
98
NEXT OP
MODE
MPrcVal
26
NxROpMod
Next room operating
mode
Protect
--
1:Protect
2:Economy
3:PrComfrt
4:Comfort
--
--