Application
Supply Chains for Primary Plants / Room
Supply Chain Coordination - Supply Air: Group Member
72
Siemens Industry, Inc.
Application Note
A6V11692053
Smart Infrastructure – Building Products
2019-04-01
Supply Chain Coordination - Supply Air: Group
Member
Airflow deviation signal
When the deviation calculation is enabled, a determination is made if the setpoint
is greater than the air flow for a period of time an analog deviation value is mode
available to the central function for additional control logic or reporting.
The supply airflow deviation signal (VavSuAirFlDvn) is used for fan speed (static
pressure) reset strategies at the air handling unit. It is obtained by measuring the
airflow from the supply duct and comparing it to the airflow setpoint.
VavSuAirFlDvn (in percent) = VavSuSpAflRel minus VavSuAirFlRel
VavSuAirFlDvn will equal 0 in case of invalid condition
Dual Duct Saturation signal
When the saturation level calculation is enabled, a determination is made if the
VAV box is starved (damper open greater than the saturation level value, i.e. not
sufficient air ) or satisfied. After saturation conditions are met (time delay
DlyOnStrtn), the saturation signal, VavSuAflStrtn1, VavSuAflStrtn2 is set to True
(starved) and can be shared via grouping with the central function to provide
additional control such as AHU static pressure reset.
Each saturation signal (VavSuAflStrtn1 and VavSuAflStrtn2) is a binary object
that is True ("Starved") when the air flow control loop cannot get enough air to
reach setpoint for a time exceeding a built-in time delay. After the delay expires,
open loop operation begins.
NOTE:
VavSuAflStrtn1/2 is always off if parameter EnStrtnCal = 0 (No). This allows the
user to exclude a particular terminal from the saturation pressure reset system.
Relief input signal
A VAV box’s binary air flow relief object (VavSuAirFlRlf) can be set to True by the
air handling unit. This is done to relieve flow resistance in the duct system in order
to maintain proper static pressure. The VAV controller responds by increasing its
air flow setpoint (VavSuSpAirFl).
When device mode = control mode and both EnRlf (Enable relief) and
VavSuAirFlRlf equal On, VavSuSpAirFl will be set to the maximum of either its
current value or the parameter AirFlRlf.
NOTE:
Relief has no effect on the supply chain VAV air demand signal VavSuAirDmd.