Commissioning Instructions
7
Restricted
A6V12093876
Scenario
Central functions &
Groups
Group objects sent from
CenOpMod to Room
Group objects sent
from Room to Segment
DelayTime (default)
Single CF
DXR
with 1 Group
CenOpMod(1)
COOLDWN (CoolDwnReq)
WARMUP (WarmupReq)
NEXT OP (NxOpMod)
RM OPMODE (ROpMod)
PLANT MODE (PltOpMod)
10 sec
Grp1
CenOpOssc11
Single CF
DXR
with 4 Groups
CenOpMod(1)
COOLDWN (CoolDwnReq)
WARMUP (WarmupReq)
NEXT OP (NxOpMod)
RM OPMODE (ROpMod)
PLANT MODE (PltOpMod)
10 sec
Grp1
CenOpOssc11
Grp2
CenOpModDly1
COOLDWN (CoolDwnReq)
WARMUP (WarmupReq)
NEXT OP (NxOpMod)
NGT CLG REQ (NgtCReq)
FRE CLGREQ (FreeCReq)
HVAC MODE (HvacPscMod)
LIGHT MODE (LgtPscMod)
SHADING MODE (ShdPscMod)
LIGHT STRGY (LgtOpStrgy)
SHADE STRGY (ShdOpStrgy)
RM OPMODE (ROpMod)
PLANT MODE (PltOpMod)
HVAC MODE (HvacPscMod)
LIGHT MODE (LgtPscMod)
SHADING MODE
(ShdPscMod)
10 sec
Grp3
CenOpModDly2
Same as Grp2
Same as Grp2
20 sec
Grp4
CenOpModDly3
Same as Grp2
Same as Grp2
30 sec
Single CF
DXR
w/ 12
Groups*
(see NOTE)
CenOpMod(1)
COOLDWN (CoolDwnReq)
WARMUP (WarmupReq)
NEXT OP (NxOpMod)
RM OPMODE (ROpMod)
PLANT MODE (PltOpMod)
10 sec
Grp1
CenOpOssc11
Grp2
CenOpModDly1
COOLDWN (CoolDwnReq)
WARMUP (WarmupReq)
NEXT OP (NxOpMod)
NGT CLG REQ (NgtCReq)
FRE CLGREQ (FreeCReq)
HVAC MODE (HvacPscMod)
LIGHT MODE (LgtPscMod)
SHADING MODE (ShdPscMod)
LIGHT STRGY (LgtOpStrgy)
SHADE STRGY (ShdOpStrgy)
RM OPMODE (ROpMod)
PLANT MODE (PltOpMod)
HVAC MODE (HvacPscMod)
LIGHT MODE (LgtPscMod)
SHADING MODE
(ShdPscMod)
10 sec
Grp3
CenOpModDly2
Same as Grp2
Same as Grp2
20 sec
Grp4
CenOpModDly3
Same as Grp2
Same as Grp2
30 sec
CenOpMod(2)
Same as Grp1
Same as Grp1
10 sec
Grp5
CenOpOssc11
Grp6
CenOpModDly1
Same as Grp2
Same as Grp2
10 sec
Grp7
CenOpModDly2
Same as Grp2
Same as Grp2
20 sec
Grp8
CenOpModDly3
Same as Grp2
Same as Grp2
30 sec
CenOpMod(3)
Same as Grp1
Same as Grp1
10 sec
Grp9
CenOpOssc11
Grp10
CenOpModDly1
Same as Grp2
Same as Grp2
10 sec
Grp11
CenOpModDly2
Same as Grp2
Same as Grp2
20 sec
Grp12
CenOpModDly3
Same as Grp2
Same as Grp2
30 sec
CenOpMod(4)
Same as Grp1
Same as Grp1
10 sec
Grp13
CenOpOssc11
Grp14
CenOpModDly1
Same as Grp2
Same as Grp2
10 sec
Grp15
CenOpModDly2
Same as Grp2
Same as Grp2
20 sec
Grp16
CenOpModDly3
Same as Grp2
Same as Grp2
30 sec
NOTE: scenario “Single CF DXR w/ 12 Groups” can be considered 12 groups, because Grp#’s 1, 5, 9, 13 can be ignored since objects
(COOLDWN, WARMUP, NEXT OP) are already included in other groups: 2-4, 6-8, 10-12, 14-16. These groups comprise 12 groups, not 16.