Data Sheet for Application

Application Sheet
INT201
Fan coil unit with staged fan, heating and cooling coil (4 pipe) on
triac output including lighting and blinds operation
DXR2..10-101A
3 / 8
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2021-09-02
A6V10662235_en--_d_--_03
Auxiliary functions
Variants
Green Leaf (RoomOptiControl) function.
Multisegment use of DXR2 automation stations with
fan coil unit application.
Standard hot water supply chain control.
The application allows for control via centralized
commands (e.g. scheduler program for room operating
mode).
Central optimum start control provides best room
comfort at the start of occupancy.
Central operation or reset of setpoints, timed valve
kick function or outside temperature dependent
heating limit.
Central override functions for valves.
Seasonal compensation of room temperature
setpoints.
1…3 speed.
PWM constant (incl. spring return) or PWM thermal
control can be selected for valves.
The room temperature can be measured by:
o KNX PL-Link wall-mount sensor
o KNX PL-Link flush-mount room operator unit
o KNX PL-Link flush-mount sensors
o Analog extract air temperature sensor
KNX PL-Link switches for lighting and blinds
operation.
Presence can be detected by KNX PL-Link sensor
or binary sensor.
Lighting
The application allows for control via centralized
commands (e.g. scheduler program).
The application function supports runtime totalization
for each lighting group for maintenance and service
purposes (burn in/operation h/ EOL end of life cycle).
Blinds
The application allows for control via centralized
commands (e.g. scheduler program or weather
station).
Siemens devices
Legend
Type of unit
Data sheet
Product No.
Qty.
DXR2…
Compact room automation station, BACnet/IP, 230 V,
flat housing, 1 DI, 2 UI, 3 DO relays, 4 DO triacs
N9204
N9206
DXR2.E10-101A
DXR2.M10-101A
1
R1
KNX PL-Link room operator unit with temperature
sensor
N1602
QMX3.P37
1
Q2, Q3
Lighting output
2)
UP 510/13
2
Q4, Q5
Lighting output
2)
UP 510/13
2
Q6, Q7
Blinds actuator, 2 x AC 230 V, 6 A
2)
RL 521/23
1
YC
2-port, 3-port valve or 3-port valves with bypass, PN16
N4847
V..P47..
1
Motorized 3-positioning actuator for V..P47.., AC 24 V
N4864
SSP81..
1
YH
2-port, 3-port valve or 3-port valves with bypass, PN16
N4847
V..P47..
1
Motorized 3-positioning actuator for V..P47.., AC 24 V
N4864
SSP81..
1
Optional
1)
Legend
Type of unit
Data sheet
Product No.
Qty.
B1
Cable temperature sensor PVC 2 m, LG-Ni1000
N1831
QAP22
1
B3
Cable temperature sensor PVC 2 m, LG-Ni1000
N1831
QAP22
1
D1
Door/window contact, white
2)
S 290/11
3)
D2
KNX PL-Link presence detector with brightness sensor
2)
UP 258D12
1 - 4
1)
Can be combined according to available on-board I/Os on controller.
2)
Further documents on www.siemens.com/gamma-td.
3)
Type of operation (NO or NC). Multiple devices of the same type can be connected.