Data Sheet for Application

Application Sheet
INT201
Fan coil unit with staged fan, heating and cooling coil (4 pipe) on
triac output including lighting and blinds operation
DXR2..10-101A
2 / 8
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2021-09-02
A6V10662235_en--_d_--_03
Description
of functions
Basic functions
Options
HVAC
PID control for heating and cooling.
The 4 pipe system provides hot and chilled water for
the heating coil and the cooling coil.
3-position valves are controlled by triac outputs for
cooling and heating.
The fan is controlled manual on the room operator unit
or automatic in 3 speeds.
The temperature is measured in the room operator
unit.
The application allows customers to adjust the room
temperature setpoints via the room operator unit
including the operation of lighting and blinds.
The operating modes are Comfort, Pre-Comfort,
Economy and Protection.
Change of operating mode via room unit, presence
detector, window contact or central command.
The air flow for heating and cooling is operated in
sequence to the valves. Parallel operation can be
configured.
HVAC
Optimal energy efficiency by including the option for
room/supply air cascade control, presence detector or
window contact.
Optional system alarms displayed on the management
station notify building operators of possible faults.
Optional trends can be activated for room sensors.
Lighting
The application allows room users to control lighting
via a standard function switching and/or
The application allows customers to control lighting
operation via room unit.
Lighting
Optional system alarms displayed on the
management station notify building operators of
possible faults (e.g. defective electronic control gear
or lamps).
Optional trends can be activated for room lighting.
Blinds
The application allows room users to operate the
blinds via the following commands:
o Move up/down
o Step up/down
The reference model applied ensures exact
positioning of the shading products.
The application allows customers to control shading
operation via room unit.
Blinds
Optional system alarms displayed on the
management station notify building operators of
possible faults (e.g. defective actuator).
Reliable, central override of local operation only for
emergencies, service, and cleaning.
Central weather protection function preventing
damages to shading products due to high winds or
frost.
Optional trends can be activated for room blinds.