Data Sheet for Application
Application Sheet
INT201
Fan coil unit with staged fan, heating and cooling coil (4 pipe) on
triac output including lighting and blinds operation
DXR2..10-101A
1 / 8
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2021-09-02
A6V10662235_en--_d_--_03
• Heating with LTHW and cooling with CHW
• Modulating control of heating and cooling valve (4 pipe) on triac output
• Automatic or manual 3-speed fan control
• Including the control of 4 lighting zones & 2 blinds
• Room temperature and fan speed operation via KNX PL-Link room operator unit with temperature
measurement & lighting and blinds operation
Plant diagram
DXR2…
Room automation station
B1
Extract air temperature sensor
Q6, Q7
2 blinds motors
B3
Supply air temperature sensor
R
Room
D1
Window contact
R1
Room operator unit with
D2
Presence detector
temperature sensor
Q1
3-speed fan
YC
Cooling coil valve
Q2, Q3,
4 lighting zones
YH
Heating coil valve
Q4, Q5
Function diagrams
Heating/cooling valves
1-2-3 speed fan
Q
Fan output signal
SpH
Effective heating setpoint
Q1.1
Fan speed 1
TR
Room temperature
Q1.2
Fan speed 2
Y
Valve output signal
Q1.3
Fan speed 3
YC
Cooling coil valve
SpC
Effective cooling setpoint
YH
Heating coil valve
SpC
0
100
Y [%]
TR [°C]
YH
SpH
YC
SpC
0
100
Y [%]
TR [°C]
YH
SpH
YC
Q1
Q [%]
Q2
Q3