Assortment / System Description

Room pressurization and fume hood control
Pressurized room, temperature control
21
204 | 275 A6V10866237_en--_b_08
Description Object Type Default value
Extract air VAV balancing state
Indicates the state of progress of the
balancing process for this VAV box. It is
written by the controller in response to
the user-entered balance command. It
persists through a power cycle.
1:Initial
2:Balancing
3:Balanced
VavExBalSta MCnfVal 1:Initial
Extract air VAV balancing mode
Air flow value set by the air balancer
person to select the airflowsetpoint
value used when the balancing state =
balancing.
1:Maximum ventilation
2:Minimum ventilation
3:Smoke
VavExBalMod MCnfVal 1:Maximum
ventilation
Extract air VAV duct area
Duct cross-sectional area, user-
entered or calculated by controller using
the duct shape, dimension A and
dimension B values.
0...1 [m
2
], 0.0...10.76 [ft
2
]
VavExDuctArea ACnfVal 0.050 [m
2
]
0.540 [ft
2
]
Extract air VAV flow coefficient
The value used to calibrate span of
airflow measurement. The value of calc
flow coefficient is written to this object
upon the Calibrate command.
0...2
VavExFlCoef ACnfVal 0.780
Exhaust calibration