Data Sheet for Application

Application Sheet
FCU041/FCU041_H
Fan coil unit with staged fan, heating and cooling coil (4 pipe) on
triac output
DXR2..10-101A
1 / 7
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2021-09-02
A6V10662235_en--_d--_01
Heating with LTHW and cooling with CHW
Modulating control of heating and cooling valve (4 pipe) on triac output
Automatic or manual 3-speed fan control
Room temperature and fan speed operation via KNX PL-Link room operator unit with temperature
measurement
Plant diagram
Room automation station
R
Room
Extract air temperature sensor
R1
Room operator unit with
Supply air temperature sensor
temperature sensor
Window contact
YC
Cooling coil valve
Presence detector
YH
Heating coil valve
3-speed fan
Function diagrams
Heating/cooling valves
1-2-3-speed fan
Fan output signal
SpH
Effective heating setpoint
Fan speed 1
TR
Room temperature
Fan speed 2
Y
Valve output signal
Fan speed 3
YC
Cooling coil valve
Effective cooling setpoint
YH
Heating coil valve
SpC
0
100
Y [%]
TR [°C]
YH
SpH
YC
SpC
0
100
Y [%]
TR [°C]
YH
SpH
YC
Q1
Q [%]
Q2
Q3