Data Sheet for Application

Application Sheet
FCU032/FCU032_H
Fan coil unit with variable fan, heating/cooling coil (2 pipe) on triac
output and electric reheater
DXR2..09T-101A
2 / 6
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2021-09-08
A6V10662233_en--_e_--_02
Description
of functions
Basic functions
Options
PID control for heating and cooling.
The 2 pipe system provides hot and chilled water for
the heating/cooling coil.
3-position valves are controlled by triac outputs for
heating and cooling.
The fan is controlled manual on the room operator unit
or automatic with variable speed.
The temperature is measured in the room operator
unit.
The application allows customers to adjust the room
temperature setpoints via the room operator unit.
The operating modes are Comfort, Pre-Comfort,
Economy and Protection.
Changeover managed by central functions distributed
over BACnet grouping.
Change of operating mode via room unit, presence
detector, window contact or central command.
The air flow for heating and cooling is operated in
sequence to the valves. Parallel operation can be
configured.
1-stage electric reheater.
Optimal energy efficiency by including the option for
room/supply air cascade control, presence detector or
window contact.
Optional system alarms displayed on the management
station notify building operators of possible faults.
Optional trends can be activated for room sensors.
Auxiliary functions
Variants
Green Leaf (RoomOptiControl) function.
Multisegment use of DXR2 automation stations with
fan coil unit application.
Standard hot and cold water supply chain control.
The application allows for control via centralized
commands (e.g. scheduler program for room operating
mode).
Central optimum start control provides best room
comfort at the start of occupancy.
Central operation or reset of setpoints, timed valve
kick function or outside temperature dependent
heating limit.
Central override functions for valves.
Seasonal compensation of room temperature
setpoints.
PWM constant (incl. spring return) or PWM thermal
control can be selected for valves.
The room temperature can be measured by:
o KNX PL-Link wall-mount sensor
o KNX PL-Link flush-mount room operator unit
o KNX PL-Link flush-mount sensors
o Analog extract air temperature sensor
Presence can be detected by KNX PL-Link sensor or
binary sensor.
Siemens devices
Legend
Type of unit
Data sheet
Product No.
Qty.
DXR2…
Compact room automation station, BACnet/IP,
230 V,
flat housing, 1 DI, 2 UI, 1 DO relay, 4 DO triacs,
1 AO 0…10 V
N9204
N9206
DXR2.E09T-101A
DXR2.M09T-101A
1
R1
KNX PL-Link room operator unit with temperature
sensor, segmented backlit display, touchkeys
N1602
QMX3.P34
1
YHC
2-port, 3-port valve or 3-port valves with bypass,
PN16
N4847
V..P47..
1
Motorized 3-positioning actuator for V..P47.., AC
24 V
N4864
SSP81..
1