Data Sheet for Application
Application Sheet
FCU032/FCU032_H
Fan coil unit with variable fan, heating/cooling coil (2 pipe) on triac
output and electric reheater
DXR2..09T-101A
2 / 6
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2021-09-08
A6V10662233_en--_e_--_02
Description
of functions
Basic functions
Options
• PID control for heating and cooling.
• The 2 pipe system provides hot and chilled water for
the heating/cooling coil.
• 3-position valves are controlled by triac outputs for
heating and cooling.
• The fan is controlled manual on the room operator unit
or automatic with variable speed.
• The temperature is measured in the room operator
unit.
• The application allows customers to adjust the room
temperature setpoints via the room operator unit.
• The operating modes are Comfort, Pre-Comfort,
Economy and Protection.
• Changeover managed by central functions distributed
over BACnet grouping.
• Change of operating mode via room unit, presence
detector, window contact or central command.
• The air flow for heating and cooling is operated in
sequence to the valves. Parallel operation can be
configured.
• 1-stage electric reheater.
• Optimal energy efficiency by including the option for
room/supply air cascade control, presence detector or
window contact.
• Optional system alarms displayed on the management
station notify building operators of possible faults.
• Optional trends can be activated for room sensors.
Auxiliary functions
Variants
• Green Leaf (RoomOptiControl) function.
• Multisegment use of DXR2 automation stations with
fan coil unit application.
• Standard hot and cold water supply chain control.
• The application allows for control via centralized
commands (e.g. scheduler program for room operating
mode).
• Central optimum start control provides best room
comfort at the start of occupancy.
• Central operation or reset of setpoints, timed valve
kick function or outside temperature dependent
heating limit.
• Central override functions for valves.
• Seasonal compensation of room temperature
setpoints.
• PWM constant (incl. spring return) or PWM thermal
control can be selected for valves.
• The room temperature can be measured by:
o KNX PL-Link wall-mount sensor
o KNX PL-Link flush-mount room operator unit
o KNX PL-Link flush-mount sensors
o Analog extract air temperature sensor
• Presence can be detected by KNX PL-Link sensor or
binary sensor.
Siemens devices
Legend
Type of unit
Data sheet
Product No.
Qty.
DXR2…
Compact room automation station, BACnet/IP,
230 V,
flat housing, 1 DI, 2 UI, 1 DO relay, 4 DO triacs,
1 AO 0…10 V
N9204
N9206
DXR2.E09T-101A
DXR2.M09T-101A
1
R1
KNX PL-Link room operator unit with temperature
sensor, segmented backlit display, touchkeys
N1602
QMX3.P34
1
YHC
2-port, 3-port valve or 3-port valves with bypass,
PN16
N4847
V..P47..
1
Motorized 3-positioning actuator for V..P47.., AC
24 V
N4864
SSP81..
1