User Manual

Application Sheet CBP002
Passive chilled/heating beam (2 pipe) with changeover on triac
output
DXR2..09T-101A
5 / 6
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2019-02-21
A6V10662233_en--_b_--_09
Optional
configuration
Equipment Values/Range Template settings
On-board output Chilled/heating beam valve position 2 Chilled; Y1, Y2; 3-position
Chilled; Y3, Y4; 3-position
Chilled; Y2; Pulse width modulation thermal
Chilled; Y3; Pulse width modulation thermal
Heating/chilled 2-pipe; Y1, Y2; 3-position
Heating/chilled 2-pipe; Y3, Y4; 3-position
Heating/chilled 2-pipe; Y2; Pulse width
modulation thermal
Heating/chilled 2-pipe; Y3; Pulse width
modulation thermal
Heating; Y1, Y2; 3-position
Heating; Y3, Y4; 3-position
Heating; Y2; Pulse width modulation thermal
Heating; Y3; Pulse width modulation thermal
Chilled beam passive; Y1, Y2; 3-position
Chilled beam passive; Y3, Y4; 3-position
Chilled beam passive; Y2; Pulse width
modulation thermal
Chilled beam passive; Y3; Pulse width
modulation thermal
Heat/chilled beam passive 2-pipe; Y1, Y2; 3-
position
Heat/chilled beam passive 2-pipe; Y3, Y4; 3-
position
Heat/chilled beam passive 2-pipe; Y2; PWM
thermal
Heat/chilled beam passive 2-pipe; Y3; PWM
thermal
Heat/chilled beam passive
2-pipe; Y3, Y4; 3-position
On-board input
Presence detector 2 (D2
a
)
X1, Normally open
Window contact (D1) D1; Normally closed
Condensation monitor (D3.1, D3.2) X2; Normally closed
KNX PL-Link devices Sensor device 1…4 (D2) UP 258D12
Default values
Parameter Values/Range Template settings
Temperature setpoints Cooling setpoint for Comfort 0 … 50 °C 24 °C
Delta cooling setpoint for Pre-comfort 0 … 10 K 1 K
Cooling setpoint for Economy 0 … 50 °C 35 °C
Cooling setpoint for Protection 0 … 50 °C 40 °C
Heating setpoint for Comfort 0 … 50 °C 21 °C
Delta heating setpoint for Pre-comfort 0 … 10 K 1 K
Heating setpoint for Economy 0 … 50 °C 15 °C
Heating setpoint for Protection 0 … 50 °C 12 °C
Chilled/heating beam Enable condensation monitor input Yes, No Yes