User Manual

Application Sheet CBP001
Passive chilled beam (2 pipe) with hot water radiator on triac output
DXR2..09T-101A
5 / 6
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2019-02-21
A6V10662233_en--_b_--_08
Default values
Parameter Values/Range Template settings
Temperature setpoints Cooling setpoint for Comfort 0 … 50 °C 24 °C
Delta cooling setpoint for Pre-comfort 0 … 10 K 1 K
Cooling setpoint for Economy 0 … 50 °C 35 °C
Cooling setpoint for Protection 0 … 50 °C 40 °C
Heating setpoint for Comfort 0 … 50 °C 21 °C
Delta heating setpoint for Pre-comfort 0 … 10 K 1 K
Heating setpoint for Economy 0 … 50 °C 15 °C
Heating setpoint for Protection 0 … 50 °C 12 °C
Radiant ceiling Enable condensation monitor input Yes, No Yes
Room operator unit Room unit, display temperature None
Display room temperature
Display room temperature
Room unit, display windows status Yes, No No
Room unit, display heat./cool. status Yes, No Yes
Enable operation: room temp.
setpoint
Yes, No Yes
Room unit, room temp. setpoint
display
Absolute temperature setpoint
Relative setpoint shift
Relative setpoint shift
Enable operation: fan speed setpoint Yes, No No
Enable operation: presence button Yes, No No
Enable operation: temporary Comfort Yes, No No
Enable operation: room op. mode Yes, No No
Enable operation: Green Leaf Yes, No Yes
Engineering ABT Site engineering tool is required to configure the DXR2 automation stations.
See the Siemens Download Center at www.siemens.com/bt/download for the latest application configuration and
workflow tutorials.
Option combination according to available on-board I/Os on controller.
D2
a
(on-board presence detector) to be configured in ABT Site under ‚Presence detector 2‘ for maximum
combination of optional devices.
Type of operation (NO or NC). Multiple devices of the same type can be connected.
Management
station
Sample presentation of a passive chilled beam with hot water radiator application on the Desigo CC management
station.