Data Sheet for Application

Application Sheet
INT061
Chilled ceiling with hot water radiator on triac output including
lighting and blinds operation
DXR2..09T-101A
2 / 8
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2021-09-02
A6V10662233_en--_e_--_07
Description
of functions
Basic functions
Options
HVAC
PID control for heating and cooling.
3-position valves are controlled by triac outputs for
radiator heating and chilled ceiling cooling.
The temperature is measured in the room operator
unit.
The application allows customers to adjust the room
temperature setpoints via the room operator unit
including the operation of lighting and blinds.
The operating modes are Comfort, Pre-Comfort,
Economy and Protection.
Change of operating mode via room unit, presence
detector, window contact or central command.
Downdraft compensation.
Outside temperature (for downdraft compensation)
distributed over BACnet.
HVAC
Condensation monitoring.
Optimal energy efficiency by presence detector or
window contact.
Optional system alarms displayed on the management
station notify building operators of possible faults.
Optional trends can be activated for room sensors.
Lighting
The application allows room users to control lighting
via a standard function switching and/or
The application allows customers to control lighting
operation via room unit.
Lighting
Optional system alarms displayed on the
management station notify building operators of
possible faults (e.g. defective electronic control gear
or lamps).
Optional trends can be activated for room lighting.
Blinds
The application allows room users to operate the
blinds via the following commands:
o Move up/down
o Step up/down
The reference model applied ensures exact
positioning of the shading products.
The application allows customers to control shading
operation via room unit.
Blinds
Optional system alarms displayed on the
management station notify building operators of
possible faults (e.g. defective actuator).
Reliable, central override of local operation only for
emergencies, service, and cleaning.
Central weather protection function preventing
damages to shading products due to high winds or
frost.
Optional trends can be activated for room blinds.
Auxiliary functions
Variants
Green Leaf (RoomOptiControl) function.
Multisegment use of DXR2 automation stations.
Standard hot water supply chain control.
The application allows for control via centralized
commands (e.g. scheduler program for room operating
mode).
Central optimum start control provides best room
comfort at the start of occupancy.
Central operation or reset of setpoints, timed valve
kick function or outside temperature dependent
heating limit.
Central override functions for valves.
Seasonal compensation of room temperature
setpoints.
PWM constant (incl. spring return) or PWM thermal
control can be selected for valves.
The room temperature can be measured by:
o KNX PL-Link wall-mount sensor
o KNX PL-Link flush-mount room operator unit
o KNX PL-Link flush-mount sensors
KNX PL-Link switches for lighting and blinds
operation.
Presence can be detected by KNX PL-Link sensor or
binary sensor.
Lighting
The application allows for control via centralized
commands (e.g. scheduler program).
The application function supports runtime totalization
for each lighting group for maintenance and service
purposes (burn in/operation h/ EOL end of life cycle).
Blinds
The application allows for control via centralized
commands (e.g. scheduler program or weather
station).