Assortment / System Description

Room pressurization and fume hood control
Fume hood
21
A6V10866237_en--_b_08 213 | 275
Description Parameter Default value
Value to display
1:Blank
2:Face velocity
3:Exhaust air volume flow
4:Exhaust level
5:Differential air pressure
Alarms will still be displayed at the ODP if set to
Blank.
DspyValue 2:Face velocity
Switch-on delay for sash opening alert
The length of time after FhSashOpnAlrt turns on
before the buzzer will start to beep. It is also the time
after the buzzer silence is pressed in response to a
sash open alert before the buzzer will start beeping
again.
DlyOnSashAlrt 300 [s]
Enable sash tone
0:No
1:Yes
Set to yes to allow the buzzer to be activated in
the event of a sash opening alert or in the event of a
sash maximum opening alert.
EnSashTone 0:No
Switch-off delay for sash maximum opening buzzer
The buzzer will be immediately turned on in the
event of a sash maximum opening alert. The buzzer
will be automatically silenced after the time defined.
The auto silence feature is disabled when
DlyOffSshmBzz is set to 0.
DlyOffSshmBzz 0 [s]
Air velocity unit
Defined by selected engineering unit – do not
change.
AirVUnit [m/s]
[ft/min]
Air volume flow unit
Defined by selected engineering unit – do not
change.
AirFlUnit [m
3
/h]
[ft
3
]
[l/s]