User Manual
Application Sheet RAD012
Hot water radiator on analog output
DXR2..09-
101A
4 / 6
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2019-02-21
A6V10662231_en--_c_--_07
Application
configuration
Equipment Values/Range Template settings
On-board output Radiator valve position 1 Water; Y20; 0...10 V
Water; Y30; 0...10 V
Electric modulating; Y20; 0...10 V
Electric modulating; Y30; 0...10 V
Water; Y20; 0...10 V
KNX PL-Link devices Room operator unit device 1 QMX3.P02, QMX3.P34, QMX3.P36, QMX3.P37,
QMX3.P74
QMX3.P34
Optional
configuration
Equipment Values/Range Template settings
On-board output Radiator valve position 2 Water; Y20; 0...10 V
Water; Y30; 0...10 V
Electric modulating; Y20; 0...10 V
Electric modulating; Y30; 0...10 V
Water; Y30; 0...10 V
On-board input
Presence detector 2 (D2
a
)
X1, Normally open
Window contact (D1) D1; Normally closed
KNX PL-Link devices Sensor device 1…4 (D2) UP 258D12
Default values
Parameter Values/Range Template settings
Temperature setpoints Heating setpoint for Comfort 0 … 50 °C 21 °C
Delta heating setpoint for Pre-comfort 0 … 10 K 1 K
Heating setpoint for Economy 0 … 50 °C 15 °C
Heating setpoint for Protection 0 … 50 °C 12 °C
Room operator unit Room unit, display temperature None
Display room temperature
Display room temperature
Room unit, display windows status Yes, No No
Room unit, display heat./cool. status Yes, No Yes
Enable operation: room temp.
setpoint
Yes, No Yes
Room unit, room temp. setpoint
display
Absolute temperature setpoint
Relative setpoint shift
Relative setpoint shift
Enable operation: fan speed setpoint Yes, No No
Enable operation: presence button Yes, No No
Enable operation: temporary Comfort Yes, No No
Enable operation: room op. mode Yes, No No
Enable operation: Green Leaf Yes, No Yes