Data Sheet for Application

Application Sheet
CBP003/CBP003_H
Passive chilled/heating beam (4 pipe) with 6-way valve on analog
output
DXR2..09-101A
2 / 7
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2021-08-26
A6V10662231_en--_c_--_12
Description
of functions
Basic functions
Options
PID control for heating and cooling.
6-way valves 0...10 V controlled by analog outputs for
heating and cooling.
The temperature is measured in the room operator
unit.
The application allows customers to adjust the room
temperature setpoints via the room operator unit.
The operating modes are Comfort, Pre-Comfort,
Economy and Protection.
Change of operating mode via room unit, presence
detector, window contact or central command.
2
nd
passive chilled/heating beam.
Condensation monitoring.
Optimal energy efficiency by presence detector or
window contact.
Optional system alarms displayed on the management
station notify building operators of possible faults.
Optional trends can be activated for room sensors.
Auxiliary functions
Variants
Green Leaf (RoomOptiControl) function.
Multisegment use of DXR2 automation stations.
The application allows for control via centralized
commands (e.g. scheduler program for room operating
mode).
Central optimum start control provides best room
comfort at the start of occupancy.
Central operation or reset of setpoints, timed valve
kick function.
Central override functions for valves.
Seasonal compensation of room temperature
setpoints.
The room temperature can be measured by:
o KNX PL-Link wall-mount sensor
o KNX PL-Link flush-mount room operator unit
o KNX PL-Link flush-mount sensors
Presence can be detected by KNX PL-Link sensor or
binary sensor.
Siemens devices
Legend
Type of unit
Data sheet
Product No.
Qty.
DXR2…
Compact room automation station, BACnet/IP,
230 V,
flat housing, 1 DI, 2 UI, 3 DO relays, 3 AO 0…10
V
N9204
N9206
DXR2.E09-101A
DXR2.M09-101A
1
R1
KNX PL-Link room operator unit with temperature
sensor, segmented backlit display, touchkeys
N1602
QMX3.P34
1
YHC1
6-way valve
A6V10564480
VWG41.20..
1
Electromotive actuator, AC 24 V, DC 0...10 V
N4657
GDB161.9E
1
Optional
1)
Legend
Type of unit
Data sheet
Product No.
Qty.
D1
Door/window contact, white
2)
S 290/11
3)
D2
KNX PL-Link presence detector with brightness
sensor
2)
UP 258D12
1 - 4
D3.1
Condensation monitor
A6V10741072
QXA21..
1
D3.2
Condensation monitor
A6V10741072
QXA21..
1
YHC2
6-way valve
A6V10564480
VWG41.20..
1
Electromotive actuator, AC 24 V, DC 0...10 V
N4657
GDB161.9E
1
1)
Can be combined according to available on-board I/Os on controller.
2)
Further documents on www.siemens.com/gamma-td.
3)
Type of operation (NO or NC). Multiple devices of the same type can be connected.