Data Sheet for Application

Application Sheet
CCG012/CCG012_H
Chilled ceiling on analog output
DXR2..09-101A
4 / 6
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2021-08-27
A6V10662231_en--_e_--_08
Application
configuration
Equipment
Values/Range
Template settings
On-board output
Radiant ceiling valve position 1
Chilled; Y20; 0...10 V
Chilled; Y30; 0...10 V
Heating/chilled 2-pipe; Y20; 0...10 V
Heating/chilled 2-pipe; Y30; 0...10 V
Heating/chilled 4-pipe 6-way; Y20; 0...10 V
Heating/chilled 4-pipe 6-way; Y30; 0...10 V
Heating; Y20; 0...10 V
Heating; Y30; 0...10 V
Chilled; Y20; 0...10 V
KNX PL-Link devices
Room operator unit device 1
QMX3.P02, QMX3.P34, QMX3.P36, QMX3.P37,
QMX3.P74
QMX3.P34
Optional
configuration
Equipment
Values/Range
Template settings
On-board output
Radiant ceiling valve position 2
Chilled; Y20; 0...10 V
Chilled; Y30; 0...10 V
Heating/chilled 2-pipe; Y20; 0...10 V
Heating/chilled 2-pipe; Y30; 0...10 V
Heating/chilled 4-pipe 6-way; Y20; 0...10 V
Heating/chilled 4-pipe 6-way; Y30; 0...10 V
Heating; Y20; 0...10 V
Heating; Y30; 0...10 V
Chilled; Y30; 0...10 V
On-board input
Presence detector 2 (D2
a
)
X1, Normally open
Window contact (D1)
D1; Normally closed
Condensation monitor (D3.1, D3.2)
X2; Normally closed
KNX PL-Link devices
Sensor device 1…4 (D2)
UP 258D12
Default values
Parameter
Values/Range
Template settings
Temperature setpoints
Cooling setpoint for Comfort
0 … 50 °C
24 °C
Delta cooling setpoint for Pre-comfort
0 … 10 K
1 K
Cooling setpoint for Economy
0 … 50 °C
35 °C
Cooling setpoint for Protection
0 … 50 °C
40 °C
Radiant ceiling
Enable condensation monitor input
Yes, No
Yes
Room operator unit
Room unit, display temperature
None
Display room temperature
Display room temperature
Room unit, display windows status
Yes, No
No
Room unit, display heat./cool. status
Yes, No
Yes
Enable operation: room temp.
setpoint
Yes, No
Yes
Room unit, room temp. setpoint
display
Absolute temperature setpoint
Relative setpoint shift
Relative setpoint shift
Enable operation: fan speed setpoint
Yes, No
No
Enable operation: presence button
Yes, No
No
Enable operation: temporary Comfort
Yes, No
No
Enable operation: room op. mode
Yes, No
No
Enable operation: Green Leaf
Yes, No
Yes