Application Sheet FCU043
Fan coil unit with staged fan, heating and cooling coil (4 pipe) on
analog output
DXR2..09-
101A
1 / 6
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2019-02-21
A6V10662231_en--_c_--_01
∂ Heating with LTHW and cooling with CHW
∂ Modulating control of heating and cooling valve (4 pipe) on analog output
∂ Automatic or manual 3-speed fan control
∂ Room temperature and fan speed operation via KNX PL-Link room operator unit with temperature
measurement
Plant diagram
DXR2… Room automation station R Room
B1 Extract air temperature sensor R1 Room operator unit with
B3 Supply air temperature sensor temperature sensor
D1 Window contact YC Cooling coil valve
D2 Presence detector YH Heating coil valve
Q1 3-speed fan
Function diagrams Heating/cooling valves 1-2-3-speed fan
Q Fan output signal SpH Effective heating setpoint
Q1 Fan speed 1 TR Room temperature
Q2 Fan speed 2 Y Valve output signal
Q3 Fan speed 3 YC Cooling coil valve
SpC Effective cooling setpoint YH Heating coil valve