Data Sheet for Product
8
Siemens
A6V11393929_en--_f
Smart Infrastructure
2021-12-03
Technical data
Power data
Power supply
Operating voltage (SELV/PELV)
AC 24 V +/-20 %
Frequency
50 or 60 Hz
Power consumption
5.5 VA max.: DXR1.M09PDZ-112, DXR1.M09PDZ-113
6 VA max.: DXR1.M09PLZ-112
Transformer requirements and recommended voltages
Type
Class 2, AC 24 V, 50 / 60 Hz, SELV, PELV
Functional data
Functional data
Nominal torque
5 Nm / 10 Nm
Nominal rotary angle
90 °
Maximum rotary angle
95 ° ± 2 °
Runtime for 90 ° rotary angle
150 s
Shaft size
8…16 mm, round
8…10 mm, round (with centering insert)
6…12.8 mm square
Minimum shaft length
20 mm
Universal inputs
Analog inputs: DC 0…10 V
Operating range
0…10 V
Resolution
10 mV
Analog inputs: sensors
Type
Measuring range
Accuracy
Resolution
LG / DIN-Ni 1000
0…50 ℃
+/- 0.5 K at 25 ℃
0.1 K at 25 ℃
Pt1K, 375 / 385
NTC10K / NTC100K
Digital inputs
0/1 digital signal (binary)
For potential-free contacts
Sampling voltage/current
DC 15 V, 7 mA