Data Sheet for Product

10
Siemens
A6V11393929_en--_f
Smart Infrastructure
2021-12-03
Connections
Interfaces
MS/TP
Terminal: 5.08 mm, 3 pin
Cable: RS485 shielded STP twisted pair, 18 AWG
Maximum network length :1000 m
Point to point length: 500 m
Termination resistor: 120 Ω
Bitrates: max. 115.2 kbps
USB (2.0)
Type Micro B
Interface for room unit (QMA1.N30H and
QMX1.M34H)
RJ45 (shield CAT 5-E)
Max. wiring length: 30 m
Default network settings
Mac address
Auto
Baud rate
76800
Network number
1
Wiring connections
Wiring lengths for signals
MS/TP: max. 1000 m
Signal lines: max. 80 m
For analog inputs: max. 30 m
Conformity
Ambient conditions and protection classification
Classification per IEC/EN 60730
Function of automatic control devices
Pollution degree
Overvoltage category
Type 1
2
III
Design type
Device suited for use with equipment of safety
classes I and II
Degree of protection of housing to IEC EN 60529
Room automation station
IP20
Climatic ambient conditions
Transport (packaged for transport) as per
IEC EN 60721-3-2
Operation as per IEC/EN 60721-3-3
Class 2K3
Temperature -25...70 °C
Air humidity 5...95 % (non-condensing)
Class 3K5
Temperature -5...50 °C
Air humidity 5...95 % (non-condensing)
Mechanical ambient conditions
Transport as per IEC/EN 60721-3-2
Operation as per IEC/EN 60721-3-3
Class 2M2
Class 3M2