User Manual

8
Siemens A6V11393929_en--_c
Smart Infrastructure 2020-09-01
Outputs
Analog output
Control range 0…10 V
Resolution 5 mV
Output current Max. 1 mA
Triac outputs
Number of channels 4
Type Requires AC 24 V source to allow switching: switching
to phase (AC 24 V) or neutral ()
Current rating 0.5 A max. per channel
Voltage rating AC 24 V +/-20 %
Max. load 12 VA per channel
Pressure sensor
Pressure sensor
Measurement range 0…500 Pa
Sample rate 500 ms
Overload range 0…100 kPa
Measuring range accuracy
Zero point accuracy
Resolution
3 %
0.2 Pa
12 Bit
Connections
Interfaces
MS/TP Terminal: 5.08 mm, 3 pin
Cable: RS485 shielded STP twisted pair, 18 AWG
Maximum network length :1000 m
Point to point length: 500 m
Termination resistor: 120
Bitrates: max. 115.2 kbps
USB (2.0) Type Micro B
Interface for room unit (QMA1.N30H and QMX1.M34H) RJ45 (shield CAT 5-E)
Max. wiring length: 30 m
Default network settings
Mac address Auto
Baud rate 76800
Network number 1
Wiring connections
Wiring lengths for signals MS/TP: max. 1000 m
Signal lines: max. 80 m
For analog inputs: max. 30 m