User Manual
8
Siemens
A6V11393929_en--_d
Smart Infrastructure
2020-12-16
Triac outputs
Number of channels
4
Type
Requires AC 24 V source to allow switching: switching
to phase (AC 24 V) or neutral (⏊)
Current rating
0.5 A max. per channel
Voltage rating
AC 24 V +/-20 %
Max. load
12 VA per channel
Pressure sensor
Pressure sensor
Measurement range
0…500 Pa
Sample rate
≤ 500 ms
Overload range
0…100 kPa
Measuring range accuracy
Zero point accuracy
Resolution
3 %
0.2 Pa
12 Bit
Connections
Interfaces
MS/TP
Terminal: 5.08 mm, 3 pin
Cable: RS485 shielded STP twisted pair, 18 AWG
Maximum network length :1000 m
Point to point length: 500 m
Termination resistor: 120 Ω
Bitrates: max. 115.2 kbps
USB (2.0)
Type Micro B
Interface for room unit (QMA1.N30H and
QMX1.M34H)
RJ45 (shield CAT 5-E)
Max. wiring length: 30 m
Default network settings
Mac address
Auto
Baud rate
76800
Network number
1
Wiring connections
Wiring lengths for signals
MS/TP: max. 1000 m
Signal lines: max. 80 m
For analog inputs: max. 30 m
Conformity
Ambient conditions and protection classification
Classification per IEC/EN 60730
Function of automatic control devices
Pollution degree
Overvoltage category
Type 1
2
III
Design type
Device suited for use with equipment of safety