Differential pressure sensor
● Avoid bends and pressure when attaching the tube.
● Connect the "+" connection on the side with the higher pressure and the "-" connection
on the side with the lower pressure.
● Connection tubes (interior diameter) of 4 mm.
Air tube connection kit DXA.T50 for connection of tubes with 6.5 mm (interior diameter).
● The maximum tube length is 2 m.
Installation
Applies to devices with supply output (AC 24 V or mains voltage) such as Triac output or
output to supply a field device.
WARNING
No internal line protection for supply lines to external consumers
Risk of fire and injury due to short-circuits
● Adapt the line diameters as per local regulations to the rated value of the installed fuse.
Maintenance
The automation station is maintenance-free.
Disposal
The device is considered an electronic device for disposal in accordance
with the European Guidelines and may not be disposed of as domestic
garbage.
● Dispose of the device through channels provided for this purpose.
● Comply with all local and currently applicable laws and regulations.