User Manual

Application Sheet
FPB053
Fan powered box with variable speed fan and staged electric reheater
DXR1.E10PL-113
9 / 11
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2020-09-01
A6V11804340_en--_b
Optional
configuration
Equipment
Channel/Signal
Settings example
VAV box extract
GDB181.1E/KN; Air volume flow control
GLB181.1E/KN; Air volume flow control
GDB181.1E/KN; Position control
GLB181.1E/KN; Position control
Radiant ceiling device
GDB111.9E/KN
HVAC
Chilled water
Heating/cooling coil
Chilled water cooling coil 11
Chilled water cooling coil 12, sply.temp
Heating/cooling coil 2-pipe system 11
Heat/cool.coil 2-pipe sys.12, sply.temp.
Heating/cooling coil 4-pipe system 13
Heat/cool.coil 4-pipe sys.14, sply.temp.
Ceiling
Chilled ceiling with chilled water 11
Ceiling heat./chilled ceiling 2-pipe 11
Ceiling heat./chilled ceiling 4-pipe 13
Ceiling heating with hot water 11
Ceiling heat./chilled ceiling 4-pipe 15
Radiator
Hot water radiator 11, mod./2-pos.ctrl.
Electric radiator 11, modulating
Electric radiator 12, one binary output
Default values
Parameter
Range
Default value
Temperature setpoints
Cooling setpoint for Comfort
0 … 50 °C
24 °C
Delta cooling setpoint for Pre-comfort
0 … 10 K
1 K
Cooling setpoint for Economy
0 … 50 °C
35 °C
Cooling setpoint for Protection
0 … 50 °C
40 °C
Heating setpoint for Comfort
0 … 50 °C
21 °C
Delta heating setpoint for Pre-comfort
0 … 10 K
1 K
Heating setpoint for Economy
0 … 50 °C
15 °C
Heating setpoint for Protection
0 … 50 °C
12 °C
Ventilation Control
Setpoint room air quality for comfort
0 … 2000 ppm
900 ppm
Setp. room air quality for pre-comfort
0 … 2000 ppm
1100 ppm
Setpoint room air quality for economy
0 … 2000 ppm
1500 ppm
Setpoint room air quality for protection
0 … 2000 ppm
1500 ppm
Supply air VAV
Supply air VAV max.air vol.flow f.cool
0 … 10’000 m
3
/h
100 m
3
/h
Supply air VAV min.air vol.flow f.cool
0 … 10’000 m
3
/h
50 m
3
/h
Supply air VAV max.air vol.flow f.heat
0 … 10’000 m
3
/h
100 m
3
/h
Supply air VAV min.air vol.flow f.heat.
0 … 10’000 m
3
/h
50 m
3
/h
Supply air VAV min.air vol.flow f.vent.
0 … 10’000 m
3
/h
0 m
3
/h
Supply air VAV flow coefficient
0 2
0.73
Room operator unit
Room unit, display temperature
None
Display room temperature
Display room temperature
Room unit, display windows status
Yes, No
No