User Manual

Application Sheet
FPB053
Fan powered box with variable speed fan and staged electric reheater
DXR1.E10PL-113
7 / 11
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2020-09-01
A6V11804340_en--_b
Optional
configuration
Equipment
Channel/Signal
Settings example
On-board output
Cooling coil valve position
Water; Y3, Y4; 3-position
Water; Y3; Pulse width modulation spring return
Water; Y10; 0...10 V
Heating and cooling coil valve
position
Water; Y3, Y4; 3-position
Water; Y5, Y6; 3-position
Water; Y3; Pulse width modulation spring return
Water; Y5; Pulse width modulation spring return
Water; Y10; 0...10 V
Enable heating coil electric position
Y3; Normally open
Y5; Normally open
Radiant ceiling valve position
Chilled; Y3, Y4; 3-position
Chilled; Y5, Y6; 3-position
Chilled; Y3; Pulse width modulation spring return
Chilled; Y5; Pulse width modulation spring return
Chilled; Y10; 0...10 V
Heating/chilled; Y3, Y4; 3-position
Heating/chilled; Y5, Y6; 3-position
Heating/chilled; Y3; Pulse width modulation
spring return
Heating/chilled; Y5; Pulse width modulation
spring return
Heating/chilled; Y10; 0...10 V
Heating; Y3, Y4; 3-position
Heating: Y5, Y6; 3-position
Heating: Y3; Pulse width modulation spring return
Heating: Y5; Pulse width modulation spring return
Heating: Y10; 0...10 V
Radiator valve position
Water; Y3, Y4; 3-position
Water; Y5, Y6; 3-position
Water; Y3; Pulse width modulation spring return
Water; Y5; Pulse width modulation spring return
Water; Y10; 0...10 V
Electric 1-stage; Y3; Normally open
Electric 1-stage; Y5; Normally open
Electric modulating; Y10; 0...10 V
Enable radiator electric position
Y3; Normally open
Y5; Normally open
On-board input
Extract air temperature (B3)
X1; Ni1000
X1; 010 V
X1; NTC100K
X1; NTC10K
X1; PT1K_EU
X1; PT1K_NA
X2; Ni1000
X2; 010 V
X2; NTC100K
X2; NTC10K
X2; PT1K_EU
X2; PT1K_NA