User Manual
Application Sheet
FPB053
Fan powered box with variable speed fan and staged electric reheater
DXR1.E10PL-113
1 / 11
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2020-09-01
A6V11804340_en--_b
Supply air volume control with integrated damper actuator (10 Nm)
Room temperature control
Air quality control
Relative humidity monitor
Room temperature and rapid ventilation operation via KNX PL-Link room operator unit with
temperature, air quality & relative humidity measurement
Plant diagram
DXR1.E10PL-113
Compact room automation stations
D4
Over-temperature detector
B1
Primary air temperature sensor
for air after treatment
D5
Enable radiator / heating coil / fan speed electric
position
D6
Fan state
B2
Supply air temperature sensor
R
Room
B3
Extract air temperature sensor
R1
Room operator unit with temperature sensor
B4
Room temperature sensor
Q1
Fan
B5
Room air quality sensor
YS
Supply air control (integrated in DXR1)
Differential pressure sensor
(supply air- integrated in DXR1)
B6
Room relative humidity sensor
YC
Cooling coil valve
B7
Mixed air temperature sensor
YHC
Heating/cooling coil valve
B8
Fan differential pressure sensor
YH
Heating coil valve/Electric reheater, 2-stage
D1
Window contact
YRC
Radiant ceiling valve
D2
Presence detector
YR
Radiator valve
D3
Condensation monitor