Data Sheet for Product

9
Siemens A6V11393933_en--_c
Smart Infrastructure 2020-09-01
Outputs
Analog output
Control range 0…10 V
Resolution 5 mV
Output current Max. 1 mA
Triac outputs
Number of channels 4
Type Requires AC 24 V source to allow switching: switching
to phase (AC 24 V) or neutral ()
Current rating 0.5 A max. per channel
Voltage rating AC 24 V +/-20 %
Max. load 12 VA per channel
Pressure sensor
Pressure sensor
Measurement range 0…500 Pa
Sample rate 500 ms
Overload range 0…100 kPa
Measuring range accuracy
Zero point accuracy
Resolution
3 %
0.2 Pa
12 Bit
Connections
Interfaces
Ethernet Plugs: dual RJ45, 10M/100M fast Ethernet
Interface type: IEEE 802.3 compliance
Cable type: 100 M STP CAT 5
USB (2.0) Type Micro B
KNX PL-Link Terminal: 5.08 mm, 2 pin
DPSU: 50 mA, non-standard DPSU
KNX PL-Link: Consider maximum bus load and different device types (two devices of the
same type are not supported).
Wiring connections
Wiring lengths for signals KNX PL-Link: max. 80 m with internal bus power
Signal lines: max. 80 m
For analog inputs: max. 30 m