Diagrams
Connection terminals
DXR1.E10PL-112 and DXR1.E10PL-113
Pin Description Terminal
1, 2 IP connection
USB USB interface
81, 82 power
24 V~
Power supply AC 24 V V~
System neutral (must always be grounded at the transformer)
91, 92 KNX PL-Link +, -
61 Digital input DI
62, 63 outputs DC 0…10 V output Y10
64…66 inputs Universal input X1, X2
54…56 Triac outputs Digital output, switching to phase (AC 24 V) or neutral () Y3, Y4
57…59 Triac outputs Digital output, switching to phase (AC 24 V) or neutral () Y5, Y6
ΔP differential pressure detector Connected to the higher pressure P1+
Connected to the lower pressure P1-
Service Service button SVC
Display Operation LED RUN