User Manual

6
Siemens A6V11393933_en--_c
Smart Infrastructure 2020-09-01
Mounting
The automation station is mounted directly on a damper shaft.
See the mounting instructions (document ID: A6V11393918) for detailed information.
Differential pressure sensor
Avoid bends and pressure when attaching the tube.
Connect the "+" connection on the side with the higher pressure and the "-" connection
on the side with the lower pressure.
Connection tubes (interior diameter) of 4 mm.
Air tube connection kit DXA.T50 for connection of tubes with 6.5 mm (interior diameter).
The maximum tube length is 2 m.
Installation
Applies to devices with supply output (AC 24 V or mains voltage) such as Triac output or
output to supply a field device.
WARNING
No internal line protec
tion for supply lines to external consumers
Risk of fire and injury due to short-circuits
Adapt the line diameters as per local regulations to the rated value of the installed fuse.
Maintenance
The automation station is maintenance-free.