LED indication
LED Color Activity Function
Run Green Steady ON Device is ready for operation
Steady OFF Device is not powered
Regular flashing Start-up or the program is stopped
Red Steady OFF OK
Steady ON Program error
Communications error (KNX PL-Link)
Hardware fault
Rapid flashing Wrong or corrupt software
No application loaded
Blinking per wink command Physical device identification
Service button (SVC)
Physical identification on the network.
Technical / Mechanical design
1 Service button (SVC) for sending device identification 2 2 UIs (universal input), 1 AO (analog output),
1 DI (digital input)
3 Power supply 4 KNX interface
5 4 DOs (digital Triac output) 6 Status information LED (bi-color)
7 2-port Ethernet switch
Housing
The housing consists essentially of flame retardant, non-brominated plastic.