Desigo™ Room Automation Compact actuating room automation stations, BACnet/IP, AC 24 V (Actuating DXR) DXR1.E10PL-112, DXR1.E10PL-113 Combination of room automation station and actuator for buildings with increasing demand on functionality and flexibility in Room Automation, VAV and FPB applications. ● ● ● ● ● ● ● ● ● ● A6V11393933_en--_c 2020-09-01 Compact, configurable room automation station in combination with actuator for HVAC QMX2.. and QMX3..
Features Configurable The DXR1.. automation stations provide the infrastructure for systems and applicationspecific functions which can be configured. Compact series The compact build allows direct mounting on the damper shaft. It is designed for VAV and FPB. Plug-in terminal blocks Plug-in terminal blocks for easy exchange of room automation stations. Integrated actuator The actuator gear base is integrated into the housing of the actuating DXR. It supports dampers with up to 10 Nm torque.
LED indication LED Color Activity Function Run Green Steady ON Device is ready for operation Steady OFF Device is not powered Regular flashing Start-up or the program is stopped Steady OFF OK Steady ON Program error Red Communications error (KNX PL-Link) Hardware fault Rapid flashing Wrong or corrupt software No application loaded Blinking per wink command Physical device identification Service button (SVC) Physical identification on the network.
Type summary Product No. Stock No. DXR1.E10PL-112 S55499-D458 2 universal inputs, Inputs DXR1.E10PL-113 S55499-D459 2 universal inputs, Outputs Description Quantity 4 digital outputs, VAV application Single package / 1 analog output multiple package (10) 1 digital input 4 digital outputs, FPB application Single package / 1 analog output multiple package (10) 1 digital input Ordering When ordering, indicate product number, stock number and description.
Product documentation Topic Title Document ID: Installation, cable length, topology Desigo Room Automation installation guide CM111043 Engineering and commissioning ABT online help N/A Installation instruction Mounting instructions A6V11393918 Commissioning Quick guide A6V11526405 Product environmental declaration A6V11805930 EU declarations (CE) A6V11791489 Documents such as environmental declarations, CE declarations, etc.
Mounting A6V11393929Z02 The automation station is mounted directly on a damper shaft. See the mounting instructions (document ID: A6V11393918) for detailed information. Differential pressure sensor ● Avoid bends and pressure when attaching the tube. ● Connect the "+" connection on the side with the higher pressure and the "-" connection on the side with the lower pressure. ● Connection tubes (interior diameter) of 4 mm. Air tube connection kit DXA.T50 for connection of tubes with 6.
Disposal The device is considered an electronic device for disposal in accordance with the European Guidelines and may not be disposed of as domestic garbage. ● Dispose of the device through channels provided for this purpose. ● Comply with all local and currently applicable laws and regulations. Warranty Technical data on specific applications are valid only together with Siemens products listed under "Equipment combinations".
Technical data Power data Power supply Operating voltage (SELV/PELV) AC 24 V +/-20 % Frequency 50 or 60 Hz Power consumption 12 VA max. Transformer requirements and recommended voltages Type Class 2, AC 24 V, 50 / 60 Hz, SELV, PELV Functional data Functional data Nominal torque 10 Nm Nominal rotary angle 90° Maximum rotary angle 95° ± 2° Runtime for 90° rotary angle 150 s Shaft size 8…16 mm, round 8…10 mm, round (with centering insert) 6…12.
Outputs Analog output Control range 0…10 V Resolution 5 mV Output current Max. 1 mA Triac outputs Number of channels 4 Type Requires AC 24 V source to allow switching: switching to phase (AC 24 V) or neutral (⏊) Current rating 0.5 A max. per channel Voltage rating AC 24 V +/-20 % Max. load 12 VA per channel Pressure sensor Pressure sensor Measurement range 0…500 Pa Sample rate ≤ 500 ms Overload range 0…100 kPa Measuring range accuracy 3% Zero point accuracy 0.
Conformity Ambient conditions and protection classification Classification per IEC/EN 60730 Function of automatic control devices Type 1 Pollution degree 2 Overvoltage category III Design type Device suited for use with equipment of safety classes I and II Degree of protection of housing to IEC EN 60529 Room automation station IP20 Climatic ambient conditions Transport (packaged for transport) as per Class 2K3 IEC EN 60721-3-2 Temperature -25...70 °C Air humidity 5...
FCC regulations Modification of this device to receive cellular radio telephone service signals is prohibited under FCC rules and federal law. This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.
Diagrams Connection terminals DXR1.E10PL-112 and DXR1.
Dimensions Dimensions in mm Siemens Smart Infrastructure 13 A6V11393933_en--_c 2020-09-01
Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug Tel. +41 58 724 2424 www.siemens.com/buildingtechnologies 14 Siemens Smart Infrastructure Document ID A6V11393933_en--_c Edition 2020-09-01 © Siemens Switzerland Ltd, 2019 Technical specifications and availability subject to change without notice.