User Manual
Application Sheet
VAV045
Supply and extract VAV with integrated damper actuator and
heating/chilled ceiling
DXR1.E10PL-112
8/24
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2020-09-01
A6V11643426_en--_b
Optional
configuration
Equipment
Channel/Signal
Settings example
Extract air VAV air volume flow
X1; 0...10 V
X2; 0...10 V
Extract air temperature (B3)
X1; Ni1000
X1; 0…10 V
X1; NTC100K
X1; NTC10K
X1; PT1K_EU
X1; PT1K_NA
X2; Ni1000
X2; 0…10 V
X2; NTC100K
X2; NTC10K
X2; PT1K_EU
X2; PT1K_NA
Primary air temperature for air after-
treatment (B1)
X1; Ni1000
X1; 0…10 V
X1; NTC100K
X1; NTC10K
X1; PT1K_EU
X1; PT1K_NA
X2; Ni1000
X2; 0…10 V
X2; NTC100K
X2; NTC10K
X2; PT1K_EU
X2; PT1K_NA
Heating coil over-temperature
detection (D4)
D1; Normally closed
X1; Normally closed
X2; Normally closed
Room air quality (B6)
X1; 0…10 V
X2; 0…10 V
Room temperature (B4)
X1; Ni1000
X1; 0…10 V
X1; NTC100K
X1; NTC10K
X1; PT1K_EU
X1; PT1K_NA
Relative humidity for room (B6)
X1; 0…10 V
X2; 0…10 V
Supply air temperature (B2)
X2; Ni1000
X2; 0…10 V
X2; NTC100K
X2; NTC10K
X2; PT1K_EU
X2; PT1K_NA
Presence detector (D2)
D1; Normally open
Radiator over-temperature detector
(D4)
D1; Normally closed
X1; Normally closed
X2; Normally closed
Condensation monitor
D1; Normally closed
X1; Normally closed
X2; Normally closed
KNX PL-Link devices
Sensor device 1 (D2)
Base module AQR2570Nx
Base module AQR2576Nx
QMX3.P30
QMX3.P70
QMX3.P40