User Manual

Application Sheet
VAV045
Supply and extract VAV with integrated damper actuator and
heating/chilled ceiling
DXR1.E10PL-112
7/24
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2020-09-01
A6V11643426_en--_b
Optional
configuration
Equipment
Channel/Signal
Settings example
On-board output
Cooling coil valve position
Water; Y3, Y4; 3-position
Water; Y3; Pulse width modulation spring return
Water; Y10; 0...10 V
Heating and cooling coil valve
position
Water; Y3, Y4; 3-position
Water; Y5, Y6; 3-position
Water; Y3; Pulse width modulation spring return
Water; Y5; Pulse width modulation spring return
Water; Y10; 0...10 V
Heating coil valve position
Water; Y3, Y4; 3-position
Water; Y5, Y6; 3-position
Water; Y3; Pulse width modulation spring return
Water; Y5; Pulse width modulation spring return
Water; Y10; 0...10 V
Electric 1-stage; Y3; Normally open
Electric 1-stage; Y5; Normally open
Electric 2-stage; Y3, Y4; Normally open
Electric 2-stage; Y5, Y6; Normally open
Electric 3-stage; Y3, Y4, Y5; Normally open
Electric 3-stage; Y4, Y5, Y6; Normally open
Electric modulating; Y10; 0...10 V
Extract air VAV position
Y1, Y2; 3-position
Y3, Y4; 3-position
Y5, Y6; 3-position
Y10; 0...10 V
Air volume flow; Y10; 0...10 V
Enable heating coil valve position
Y3; Normally open
Y5; Normally open
Radiant ceiling valve position
Chilled; Y3, Y4; 3-position
Chilled; Y5, Y6; 3-position
Chilled; Y3; Pulse width modulation spring return
Chilled; Y5; Pulse width modulation spring return
Chilled; Y10; 0...10 V
Heating/chilled; Y3, Y4; 3-position
Heating/chilled; Y5, Y6; 3-position
Heating/chilled; Y3; Pulse width modulation
spring return
Heating/chilled; Y5; Pulse width modulation
spring return
Heating/chilled; Y10; 0...10 V
Heating; Y3, Y4; 3-position
Heating: Y5, Y6; 3-position
Heating: Y3; Pulse width modulation spring return
Heating: Y5; Pulse width modulation spring return
Heating: Y10; 0...10 V
Radiator valve position
Water; Y3, Y4; 3-position
Water; Y5, Y6; 3-position
Water; Y3; Pulse width modulation spring return
Water; Y5; Pulse width modulation spring return
Water; Y10; 0...10 V
Electric 1-stage; Y3; Normally open
Electric 1-stage; Y5; Normally open
Electric modulating; Y10; 0...10 V
Enable radiator electric position
Y3; Normally open
Y5; Normally open
On-board input
Extract air VAV differential air
pressure (YE)
X1; 0...10 V
X2; 0...10 V
P1