Data Sheet for Product

9
Siemens
A6V11393931_en--_f
Smart Infrastructure
2021-11-01
Digital inputs
Contact resistance
Max. 200 Ω (closed)
Min. 50 kΩ (open)
Delay
10 ms
Pulse frequency
Max. 20 Hz
Outputs
Analog output
Control range
0…10 V
Resolution
50 mV
Output current
Max. 1 mA
Triac outputs
Number of channels
4
Type
Requires AC 24 V source to allow switching: switching
to phase (AC 24 V) or neutral ()
Current rating
0.5 A max. per channel
Voltage rating
AC 24 V +/-20 %
Max. load
12 VA per channel
Pressure sensor
Pressure sensor
Measurement range
0…500 Pa
Sample rate
≤ 500 ms
Overload range
0…100 kPa
Measuring range accuracy
Zero point accuracy
Resolution
3 %
0.2 Pa
12 Bit
Connections
Interfaces
Ethernet
Plugs: dual RJ45, 10M/100M fast Ethernet
Interface type: IEEE 802.3 compliance
Cable type: 100M STP CAT 5
USB (2.0)
Type Micro B
Interface for room unit (QMA1.N30H and QMX1.M34H)
RJ45 (shield CAT 5-E)
Max. wiring length: 30 m