Fan powered box with series fan and staged electric reheater
DXR1.M09PDZ-113
DXR1.E09PDZ-113
8 / 9
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2020-09-01
A6V11804338_en--_b
Optional
configuration
Equipment
Channel/Signal
Settings example
Supply air temperature (B2)
X2; Ni1000
X2; 0…10 V
X2; NTC100K
X2; NTC10K
X2; PT1K_EU
X2; PT1K_NA
Presence detector (D2)
X1; Normally open
X2; Normally open
Window contact (D1)
X1; Normally closed
X2; Normally closed
Fan state (D5)
X1; Normally open
X2; Normally open
Default values
Parameter
Range
Default value
Temperature setpoints
Cooling setpoint for Comfort
0 … 50 °C
24 °C
Delta cooling setpoint for Pre-comfort
0 … 10 K
1 K
Cooling setpoint for Economy
0 … 50 °C
35 °C
Cooling setpoint for Protection
0 … 50 °C
40 °C
Heating setpoint for Comfort
0 … 50 °C
21 °C
Delta heating setpoint for Pre-comfort
0 … 10 K
1 K
Heating setpoint for Economy
0 … 50 °C
15 °C
Heating setpoint for Protection
0 … 50 °C
12 °C
Ventilation Control
Setpoint room air quality for comfort
0 … 2000 ppm
900 ppm
Setp. room air quality for pre-comfort
0 … 2000 ppm
1100 ppm
Setpoint room air quality for economy
0 … 2000 ppm
1500 ppm
Setpoint room air quality for protection
0 … 2000 ppm
1500 ppm
Supply air VAV
Supply air VAV max.air vol.flow f.cool
0 … 10’000 m
3
/h
100 m
3
/h
Supply air VAV min.air vol.flow f.cool
0 … 10’000 m
3
/h
50 m
3
/h
Supply air VAV max.air vol.flow f.heat
0 … 10’000 m
3
/h
100 m
3
/h
Supply air VAV min.air vol.flow f.heat.
0 … 10’000 m
3
/h
50 m
3
/h
Supply air VAV min.air vol.flow f.vent.
0 … 10’000 m
3
/h
0 m
3
/h
Supply air VAV flow coefficient
0 … 10’000 m3/h/SqrtPa
150 m
3
/h/SqrtPa
Fan
Single speed fan operation
No (fan coil unit or heat pump)
On request (parallel fan powered VAV
box)Continuous on (series fan powered VAV box)
Continuous on