User Manual

Application Sheet
FPB052
Fan powered box with series fan and staged electric reheater
DXR1.M09PDZ-113
DXR1.E09PDZ-113
7 / 9
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2020-09-01
A6V11804338_en--_b
Optional
configuration
Equipment
Channel/Signal
Settings example
On-board output
Enable fan speed
Y4; Normally open
Y6; Normally open
Enable heating coil electric position
Y3; Normally open
Y5; Normally open
On-board input
Fan differential pressure (B8)
X1; 0...10 V
X2; 0...10 V
Extract air temperature (B3)
X1; Ni1000
X1; 0…10 V
X1; NTC100K
X1; NTC10K
X1; PT1K_EU
X1; PT1K_NA
X2; Ni1000
X2; 0…10 V
X2; NTC100K
X2; NTC10K
X2; PT1K_EU
X2; PT1K_NA
Mixed air temperature (B7)
X1; Ni1000
X1; 0…10 V
X1; NTC100K
X1; NTC10K
X1; PT1K_EU
X1; PT1K_NA
X2; Ni1000
X2; 0…10 V
X2; NTC100K
X2; NTC10K
X2; PT1K_EU
X2; PT1K_NA
Primary air temperature for air after-
treatment (B1)
X1; Ni1000
X1; 0…10 V
X1; NTC100K
X1; NTC10K
X1; PT1K_EU
X1; PT1K_NA
X2; Ni1000
X2; 0…10 V
X2; NTC100K
X2; NTC10K
X2; PT1K_EU
X2; PT1K_NA
Heating coil over-temperature detection
(D3)
X1; Normally closed
X2; Normally closed
Room air quality (B5)
X1; 0…10 V
X2; 0…10 V
Room temperature (B4)
X1; Ni1000
X1; 0…10 V
X1; NTC100K
X1; NTC10K
X1; PT1K_EU
X1; PT1K_NA
Relative air humidity for room (B6)
X1; 0…10 V
X2; 0…10 V