User Manual

Application Sheet
FPB052
Fan powered box with series fan and staged electric reheater
DXR1.M09PDZ-113
DXR1.E09PDZ-113
1 / 9
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2020-09-01
A6V11804338_en--_b
Supply air volume control with integrated damper actuator (5 Nm)
Room temperature control
Air quality control
Relative humidity monitor
Plant diagram
Compact room automation stations
DXR1.M09PDZ-113, DXR1.E09PDZ-113
D1
Window contact
D2
Presence detector
Primary air temperature sensor
for air after treatment
D3
Over-temperature detector
D4
Enable heating coilelectric position / Enable fan speed
Supply air temperature sensor
D5
Fan state
Extract air temperature sensor
R
Room
Room temperature sensor
R1
Room operator unit with temperature sensor
Room air quality sensor
Q1
Fan
Room relative humidity sensor
YH
Heating coil valve/Electric reheater, 2-stage
Mixed air temperature sensor
YS
Supply air control (integrated in DXR1)
Differential pressure sensor
(supply air integrated in DXR1..)
Fan differential pressure sensor
Function diagrams
Air flow with 2-stage electric reheater
SpC
Effective cooling setpoint
VavSuAirFlMaxH
Max. volume, heating
SpH
Effective heating setpoint
VavSuAirFlMinC
Min. volume, cooling
TR
Room temperature
VavSuAirFlMinH
Min. volume, heating
V
Volume flow rate
Y
Output signal
VavSuAflMinVent
Min. air flow ventilation
YH
Electric reheater
VavSuAirFlMaxC
Max. volume, cooling