Technical data
Power data
Power supply
Operating voltage (SELV/PELV) AC 24 V +/-20 %
Frequency 50 or 60 Hz
Power consumption 7 VA max.
Transformer requirements and recommended voltages
Type Class 2, AC 24 V, 50 / 60 Hz, SELV, PELV
Functional data
Functional data
Nominal torque 5 Nm
Nominal rotary angle 90 °
Maximum rotary angle 95 ° ± 2 °
Runtime for 90 ° rotary angle 150 s
Shaft size 8…16 mm, round
8…10 mm, round (with centering insert)
6…12.8 mm square
Minimum shaft length 20 mm
Universal inputs
Analog inputs: DC 0…10 V
Operating range 0…10 V
Resolution 10 mV
Analog inputs: sensor
Type Measuring range Accuracy Resolution
LG / DIN-Ni 1000 0…50
+/- 0.5 K at 25
0.1 K at 25
Pt1K, 375 / 385
NTC10K / NTC100K
Digital inputs
0/1 digital signal (binary) For potential free contacts
Sampling voltage/current DC 15 V, 7 mA
Contact resistance Max. 200 (closed)
Min. 50 k (open)
Delay 10 ms
Pulse frequency Max. 20 Hz
Outputs
Analog output
Control range 0…10 V
Resolution 5 mV
Output current Max. 1 mA