Desigo™ Room Automation Compact actuating room automation stations, BACnet/IP, AC 24 V (Actuating DXR) DXR1.E09PDZ-112, DXR1.E09PDZ-113 Combination of room automation station and actuator for buildings with increasing demand on functionality and flexibility in Room Automation, VAV and FPB applications. ● ● ● ● ● ● ● ● ● A6V11393931_en--_c 2020-09-01 Compact, configurable room automation station in combination with actuator for HVAC QMX1.M34H room unit and QMA1.
Features Configurable The DXR1.. automation stations provide the infrastructure for systems and applicationspecific functions which can be configured. Compact series The compact build allows direct mounting on the damper shaft. It is designed for VAV and FPB. Plug-in terminal blocks Plug-in terminal blocks for easy exchange of room automation stations. Integrated actuator The actuator gear base is integrated into the housing of the actuating DXR. It supports dampers with up to 5 Nm torque.
LED indication LED Color Activity Function Run Green Steady ON Device is ready for operation Steady OFF Device is not powered Regular flashing Start-up or the program is stopped Steady OFF OK Steady ON Program error Red Hardware fault Rapid flashing Wrong or corrupt software No application loaded Blinking per wink command Physical device identification Service button (SVC) Physical identification on the network.
Type summary Product No. Stock No. Inputs Outputs Description Quantity DXR1.E09PDZ-112 S55499-D456 2 universal inputs 4 digital outputs, VAV application Single package / 1 analog output multiple package (10) DXR1.E09PDZ-113 S55499-D457 2 universal inputs 4 digital outputs, FPB application Single package / 1 analog output multiple package (10) Ordering When ordering, indicate product number, stock number and description. Equipment combinations Product No. Stock No. Designation Datasheet* QMA1.
Engineering Identification Each device has a unique serial number to ensure efficient commissioning. It is provided on the adhesive barcode reader. The serial number can be read directly into the engineering tool using a barcode reader. Wiring Wiring must be sufficiently insulated to the available rated voltage. Sizing and fusing of the wiring depends on the connected load. Mounting A6V11393929Z02 The automation station is mounted directly on a damper shaft.
Maintenance The controller is maintenance-free. Disposal The device is considered an electronic device for disposal in accordance with the European Guidelines and may not be disposed of as domestic garbage. ● Dispose of the device through channels provided for this purpose. ● Comply with all local and currently applicable laws and regulations. Warranty Technical data on specific applications are valid only together with Siemens products listed under "Equipment combinations".
Technical data Power data Power supply Operating voltage (SELV/PELV) AC 24 V +/-20 % Frequency 50 or 60 Hz Power consumption 7 VA max. Transformer requirements and recommended voltages Type Class 2, AC 24 V, 50 / 60 Hz, SELV, PELV Functional data Functional data Nominal torque 5 Nm Nominal rotary angle 90 ° Maximum rotary angle 95 ° ± 2 ° Runtime for 90 ° rotary angle 150 s Shaft size 8…16 mm, round 8…10 mm, round (with centering insert) 6…12.
Triac outputs Number of channels 4 Type Requires AC 24 V source to allow switching: switching to phase (AC 24 V) or neutral (⏊) Current rating 0.5 A max. per channel Voltage rating AC 24 V +/-20 % Max. load 12 VA per channel Pressure sensor Pressure sensor Measurement range 0…500 Pa Sample rate ≤ 500 ms Overload range 0…100 kPa Measuring range accuracy 3% Zero point accuracy 0.
Conformity Ambient conditions and protection classification Classification per IEC/EN 60730 Function of automatic control devices Type 1 Pollution degree 2 Overvoltage category III Design type Device suited for use with equipment of safety classes I and II Degree of protection of housing to IEC EN 60529 Room automation station IP20 Climatic ambient conditions Transport (packaged for transport) as per Class 2K3 IEC EN 60721-3-2 Temperature -25...70 °C Air humidity 5...
FCC regulations Modification of this device to receive cellular radio telephone service signals is prohibited under FCC rules and federal law. This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.
Diagrams Connection terminals DXR1.E09PDZ-112 and DXR1.E09PDZ-113 Pin Description 1, 2 IP connection USB USB interface 81...
Dimensions Dimensions in mm Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug Tel. +41 58 724 2424 www.siemens.com/buildingtechnologies 12 Siemens Smart Infrastructure Document ID A6V11393931_en--_c Edition 2020-09-01 © Siemens Switzerland Ltd, 2019 Technical specifications and availability subject to change without notice.