User Manual

7
A6V11526405_en--_b
13 | 16
7 Connecting DXR1 to ABT Site
1. Go to Start up > Configure and download, and click the arrow beside the
symbol (connection settings), and select the corresponding device type
and network.
USB: select the device type PTP for both IP and MS/TP devices.
Ethernet: Select the device type: IP devices or MS/TP devices.
2. Click Connect and the device is connected successfully to ABT Site.
Note:
Once you have specified the connection settings, you can click the button
directly.
Once you have established a connection the button is toggled to .
Context menu
Right-click the device in a row, the context menu displays.
Command
Description
Restart device
Stops and restarts the device with current settings.
Clear device
Stops and clears the device, and clears the application
configuration.
Notes:
After clearing the devices is finished, the device resets to factory
status.
Flash LED
Flashes the LED on the device.
Provide authentication
Opens the Authentication dialog box. You must enter your User
name and Password to login to the device.
Discover all unconfigured devices
on network (MS/TP only)
Discovers all unaddressed MS/TP devices on the specified
network. A configured device must be selected so that the
discover unaddressed operation can be issued to other devices
on the network. All found devices will be listed in the discovered
devices table.
Notes:
1. This command applies only to DXR2.M (when working with
DXR1.M)
2. This command takes several minutes to complete and
causes the network to become unresponsive while polling.
Perform auto-addressing (MS/TP
only)
Auto addresses all unconfigured MS/TP devices on the specified
network, and only sets the network number and MAC address of
the devices. A configured device (DXR2.M) must be selected so
that the auto-address operation can be issued to other devices on
the network. Auto-addressing is for MS/TP devices only. All
addressed devices will be listed in the Discovered devices table.
Notes:
1. This command applies only to DXR2.M (when working with
DXR1.M)
2. This command takes several minutes to complete and
causes the network to become unresponsive while polling.
Set Baud rate for all devices on
network (MS/TP only)
Resets the baud rate (9600, 19200, 38400, 76800, or 115200) for
all devices on the specified network. A configured device must be
selected so that the set baud rate operation can be issued to
other devices on the network. Initially the devices set the baud
rate automatically based on the baud rate of the devices already
communicating on the network.
Notes:
1. This command applies only to DXR2.M (when working with
DXR1.M)
2. This command takes several minutes to complete.