Verify/set duct area.
a.
Locate Supply air VAV duct shape. Set Supply air VAV duct shape by
selecting from the following options and then set the related
parameters:
i.
Round (Set Supply air VAV dimension A)
ii.
Flat oval (Set Supply air VAV dimension A and Supply air VAV
dimension B)
iii.
Rectangular (Set Supply air VAV dimension A and Supply air VAV
dimension B)
iv.
Direct entry (Set Supply air VAV duct area)
Note: When setting a value less than 1, enter a leading zero and
decimal (like 0.566)
CAUTION
CAUTION:
Duct area is calculated by the application. To manually enter a different value,
you must first set the duct shape object (
VavSuDuctShape) to Direct entry and
then manually enter the desired duct area value in the duct shape object,
Supply
air VAV duct shape.
If the user manually enters a duct area value without first setting
VavSuDuctShape to Direct entry, the value may appear to be accepted by the
application but it will be overwritten by the system without informing the user!
5.7
Balancing procedure
a.
Set Supply air VAV balancing mode. Select from the following options