s Compact actuating room automation station BACnet Protocol Implementation Conformance Statement (PICS) 1/19 PICS Compact actuating room automation station 29-11-2019
Contents 1 2/19 Compact actuating room automation station 3 1.1 Product description ................................................................................... 3 1.2 BACnet standardized device profile (Annex L) ........................................... 3 1.3 BACnet interoperability building blocks supported (Annex K) ..................... 4 1.4 Standard object types supported ............................................................... 7 1.5 Segmentation capability ................
1 Compact actuating room automation station Date Vendor name Product name Product model number BACnet protocol version Application software version Firmware revision 1.1 Nov 29, 2019 Siemens (Vendor ID 7) Compact actuating room automation station DXR1.M09PDZ-112 DXR1.M09PDZ-113 DXR1.E02PLZ-112 DXR1.E09PDZ-112 DXR1.E09PDZ-113 DXR1.E10PL-112 DXR1.E10PL-113 Revision1.15 AAS-20:SU=SiUn;CPD=2019-11-07 06:14:49; FW=03.54.02.03;SVS-300.6:SBC=15.00;ISC=01.
Controllers BACnet Building Controller (B-BC) BACnet Advanced Application Controller (B-AAC) BACnet Application Specific Controller (B-ASC) BACnet Smart Actuator (B-SA) BACnet Smart Sensor (B-SS) Life Safety Controllers BACnet Advanced Life Safety Controller (B-ALSC) BACnet Life Safety Controller (B-LSC) Access Control Controllers BACnet Advanced Access Control Controller (B-AACC) BACnet Access Control Controller (B-ACC) Miscellaneous BACnet Router (B-RTR) BACnet Gateway (B-GW) BAC
1.
Alarm and Event Management Alarm and Event – Notification-A AE-N-A Alarm and Event – Notification Internal-B AE-N-I-B Alarm and Event – Notification External-B AE-N-E-B Alarm and Event – Acknowledge-A AE-ACK-A Alarm and Event – Acknowledge-B AE-ACK-B Alarm and Event – Alarm Summary-B AE-ASUM-B Alarm and Event – Enrollment Summary-B AE-ESUM-B Alarm and Event – Information-B AE-INFO-B Alarm and Event – Life Safety-A AE-LS-A Alarm and Event – Life Safety-B AE-LS-B Alarm and Event – View No
Scheduling Scheduling – Internal-B SCHED-I-B Scheduling – External-B SCHED-E-B Scheduling – Readonly-B SCHED-R-B Scheduling – Advanced View Modify-A SCHED-AVM-A Scheduling – View Modify-A SCHED-VM-A Scheduling – Weekly Schedule-A SCHED-WS-A Scheduling – Weekly Schedule Internal-B SCHED-WS-I-B Scheduling – Timer-Internal-B SCHED-TMR-I-B Scheduling – Timer-External-B SCHED-TMR-E-B Historical/Deprecated BIBBs Scheduling – A Trending SCHED-A Trending – Viewing and Modifying Internal-B T-V
Device Management 8/19 Device Management – Dynamic Device Binding-A DM-DDB-A Device Management – Dynamic Device Binding-B DM-DDB-B Device Management – Dynamic Object Binding-A DM-DOB-A Device Management – Dynamic Object Binding-B DM-DOB-B Device Management – Device Communication Control-A DM-DCC-A Device Management – Device Communication Control-B DM-DCC-B Device Management – Text Message-A DM-TM-A Device Management – Text Message-B DM-TM-B Device Management – Time Synchronization-A DM-TS
Network Management Gateway Network Security Network Management – Connection Establishment-A NM-CE-A Network Management – Connection Establishment-B NM-CE-B Network Management – Router Configuration-A NM-RC-A Network Management – Router Configuration-B NM-RC-B Network Management – BBMD Configuration-A NM-BBMDC-A Network Management – BBMD Configuration-B NM-BBMDC-B Network Management – Foreign Device Registration-A NM-FDR-A Gateway – Virtual Network-B GW-VN-B Gateway – Embedded Objects-B G
1.
Object type Supported Can be created dynamically Can be deleted dynamically Date Value Datetime Pattern Value Time Pattern Value Date Pattern Value Network Security Global Group Notification Forwarder Alert Enrollment Channel Lighting Output Binary Lighting Output Network Port Timer Elevator Group Lift Escalator Accumulator 11/19 PICS Compact actuating room automation station 29-11-2019
Analog Input Properties supported Object_Identifier Readable/ Writable R Object_Name W Object_Type R Present_Value R Description W Device_Type R Status_Flags R Event_State R Reliability R Out_Of_Service W Range restrictions Update_Interval Analog Output Units W Min_Pres_Value W Max_Pres_Value W Resolution W COV_Increment W Property_List R Profile_Name W Properties Object_Identifier 12/19 supported Readable/ Writable R Object_Name W Object_Type R Present_Value
Analog Value Binary Input Properties supported Readable/ Writable Object_Identifier R Object_Name W Object_Type R Present_Value W Description R Status_Flags R Event_State R Reliability R Out_Of_Service W Units W Priority_Array R Relinquish_Default W COV_Increment W Min_Pres_Value W Max_Pres_Value W Resolution W Property_List R Profile_Name R Properties Object_Identifier supported Range restrictions Readable/ Writable R Object_Name W Object_Type R Present_Valu
Binary Output Properties supported Object_Identifier Binary Value Object_Name W Object_Type R Present_Value W Description W Device_Type R Status_Flags R Event_State R Reliability R Out_Of_Service R Polarity R Inactive_Text R Active_Text R Minimum_Off_Time W Minimum_On_Time W Priority_Array R Relinquish_Default W Property_List R Profile_Name R Properties Object_Identifier Object_Name 14/19 Readable/ Writable R supported Readable/ Writable R Range restrictions Ra
Device Properties Object_Identifier supported Readable/ Writable W Object_Name W Object_Type R System_Status R Vendor_Name R Vendor_Identifier R Model_Name R Firmware_Revision R Application_Software_Version R Location W Description W Protocol_Version R Protocol_Revision R Protocol_Services_Supported R Protocol_Object_Types_Supported R Object_List R Structured_Object_List R Max_APDU_Length_Accepted R Segmentation_Supported R Max_Segments_Accepted R Local_Time W Loc
Loop Properties Object_Identifier 16/19 supported Readable/ Writable R Object_Name W Object_Type R Present_Value R Description W Status_Flags R Event_State R Reliability R Out_Of_Service W Output_Units W Manipulated_Variable_Reference R Controlled_Variable_Reference R Controlled_Variable_Value R Controlled_Variable_Units W Setpoint_Reference R Setpoint R Action R Proportional_Constant W Proportional_Constant_Units W Integral_Constant W Integral_Constant_Units W D
Multi-state Output Properties supported Object_Identifier Multi-state Value Readable/ Writable R Object_Name W Object_Type R Present_Value W Description W Device_Type R Status_Flags R Event_State R Reliability R Out_Of_Service W Number_Of_States R State_Text R Priority_Array R Relinquish_Default W Property_List R Profile_Name R Properties Object_Identifier Object_Name supported Readable/ Writable R Range restrictions Range restrictions R Object_Type R Present_Valu
1.5 1.6 Segmentation Capability Able to transmit segmented messages Window size 16 Able to receive segmented messages Window size 16 Data Link Layer Options The simultaneously supported Data Link Layers of a product are listed with the product model number. ARCNET (ATA 878.1), 2.5 Mb. (Clause 8) ARCNET (ATA 878.
Annex H, BACnet Tunnelling Router over IP 1.9 Character Sets Supported Indicating support for multiple character sets does not imply that they can all be supported simultaneously. UTF-8 (or ANSI X3.4) IBM / Microsoft DBCS ISO 8859-1 ISO 10646 (UCS-2) ISO 10646 (UCS-4) JIS X 0208 1.