User Manual

6
Siemens A6V11393935_en--_c
Smart Infrastructure 2020-09-01
Technical data
Power data
Power supply
Operating voltage (SELV/PELV) AC 24 V +/-20 %
Frequency 50 or 60 Hz
Power consumption 6.5 VA max.
Transformer requirements and recommended voltages
Type Class 2, AC 24 V, 50 / 60 Hz, SELV, PELV
Functional data
Functional data
Nominal torque 10 Nm
Nominal rotary angle 90°
Maximum rotary angle 95° ±
Runtime for 90° rotary angle 150 s
Shaft size 8…16 mm, round
8…10 mm, round (with centering insert)
6…12.8 mm square
Minimum shaft length 20 mm
Pressure sensor
Pressure sensor
Measurement range 0…500 Pa
Sample rate 500 ms
Overload range 0…100 kPa
Measuring range accuracy
Zero point accuracy
Resolution
3 %
0.2 Pa
12 Bit
Connections
Interfaces
Ethernet Plugs: dual RJ45, 10M/100M fast Ethernet
Interface type: IEEE 802.3 compliance
Cable type: 100M STP CAT 5
USB (2.0) Type Micro B