User Manual
6
Siemens A6V11393935_en--_c
Smart Infrastructure 2020-09-01
Technical data
Power data
Power supply
Operating voltage (SELV/PELV) AC 24 V +/-20 %
Frequency 50 or 60 Hz
Power consumption 6.5 VA max.
Transformer requirements and recommended voltages
Type Class 2, AC 24 V, 50 / 60 Hz, SELV, PELV
Functional data
Functional data
Nominal torque 10 Nm
Nominal rotary angle 90°
Maximum rotary angle 95° ± 2°
Runtime for 90° rotary angle 150 s
Shaft size 8…16 mm, round
8…10 mm, round (with centering insert)
6…12.8 mm square
Minimum shaft length 20 mm
Pressure sensor
Pressure sensor
Measurement range 0…500 Pa
Sample rate ≤ 500 ms
Overload range 0…100 kPa
Measuring range accuracy
Zero point accuracy
Resolution
3 %
0.2 Pa
12 Bit
Connections
Interfaces
Ethernet Plugs: dual RJ45, 10M/100M fast Ethernet
Interface type: IEEE 802.3 compliance
Cable type: 100M STP CAT 5
USB (2.0) Type Micro B