Mounting
The automation station is mounted directly on a damper shaft.
A
6
V
1
1
3
9
3
9
2
9
Z
0
2
See the mounting instructions (document ID: A6V11393918) for detailed information.
Differential pressure sensor
● Avoid bends and pressure when attaching the tube.
● Connect the "+" connection on the side with the higher pressure and the "-" connection
on the side with the lower pressure.
● Connection tubes (interior diameter) of 4 mm.
Air tube connection kit DXA.T50 for connection of tubes with 6.5 mm (interior diameter).
● The maximum tube length is 2 m.
Maintenance
The automation station is maintenance-free.
Disposal
The device is considered an electronic device for disposal in accordance
with the European Guidelines and may not be disposed of as domestic
garbage.
● Dispose of the device through channels provided for this purpose.