Data Sheet for Application

Application Sheet VAV011
VAV with integrated damper actuator
DXR1.E02PLZ-112
3 / 3
Technical information in this document are subject to change. Drawings serve illustration purposes only.
Siemens is not responsible for content and any manual modifications.
2021-02-19
A6V11918860_en--_b
Application
configuration
Equipment Channel/Signal Settings example
On-board output VAV position (integrated actuator) Y1, Y2; 3-position Y1, Y2; 3-position
On-board input VAV differential air pressure
(integrated sensor)
P1 P1
HVAC VAV flow VAV flow control 11 VAV flow control 11
Default values
Parameter Range Default value
HVAC VAV box coefficient 0 … 10’000 m
3
/h/SqrtPa 150 m
3
/h/SqrtPa
Engineering ABT Site engineering tool is required to configure the DXR1 automation stations.
See the Siemens Download Center at www.siemens.com/bt/download for the latest application configuration and
workflow tutorials.